Hello, in today’s smart factory, temperature monitoring and control is necessary for any factory. In the previous post, plc247.com guided you to connect HMI Proface with Omron E5CC, today plc247.com will continue to guide you to connect to Autonics TK4S .
With one display Proface GP4402WW we can connect up to 32 stations (32 different TK4S controllers).
Autonics TK4S & GP4402WW “Wiring Diagram”

Autonics TK4S Modbus RTU Setting
We need to set communication parameters for TK4S in Parameters.4 Group

Register Address Table


+ Set Temperature Address (SV) = 400001
+ Read Present Value Address (PV) = 301001
HMI Proface Modbus RTU Configuration
You configure the same communication parameters as TK4S Controller

GP4402WW HMI Programming
+ Control Page

+ TK4S No1 Set Temperature

+ TK4S No2 Set Temperature

+ TK4S No1 Read Temperature

+ TK4S No2 Read Temperature

Project Video Tutorial
======
Related Software and Documents
- Download Proface GP4402WW HMI Software
- Autonics TK4S Modbus RTU Manual PDF Download (Password: plc247.com)
Please share the article if you find it useful. If you have any difficulty in connecting GP4402WW with TK4S, please comment below the article, plc247.com will reply to you as soon as possible.
Best Regards!