Hello, in previous posts, plc247.com used HMI Proface GP4402WW to connect and control different Omron And Autonics Temperature Controllers.
Today, plc247.com will continue to guide you to use HMI GP4402WW to control Mitsubishi FR E700 Series Inverter through Modbus RTU RS485 Communication.
HMI GP4402WW & FR E720 “Wiring Diagram”
Mitsubifhi FR E700 Modbus RTU Configuration
In addition to the basic parameters of the inverter, we need to set other communication parameters as follows
+ Pr117: 1 (Slave Address)
+ Pr118: 96 (Baudrate 9600)
+ Pr119: 0 (8bit, stop bit = 1)
+ Pr120: 2 (Even)
+ Pr121: 9999
+ Pr122: 9999
+ Pr123: 9999
+ Pr124: 1
+ Pr340: 1
+ Pr549: 1
+ Pr79: 2 (Last Setting)
Registers Address Table
Note: Proface HMI – Mitsubishi FR E700 VFD
Address Using = 400001 + (VFD Address – 40001)
>>> Motor Control Address = 400001 + (40009 – 40001) = 400009
- Set Word 400009 = 2 >>> Motor Forward Run
= 4 >>> Motor Reverse Run
= 0 >>> Stop
>>> Frequency Setting Address = 400001 + (40014 – 40001) = 400014
>>> Output Frequency Address = 400001 + (40201 – 40001) = 400201
>>> Output Current Address = 400001 + (40202 – 40001) = 400202
>>> Output Voltage Address = 400001 + (40203 – 40001) = 400203
Proface HMI GP4402WW Communication Setting
You configure the communication parameters of the HMI like
FR-E700 VFD
HMI Programming
+ Control Panel
+ Setting Frequyency
+ Forward Run
+ Reverse Run
+ Stop
+ Output Frequency
+ Output Current
+ Output Voltage
Video Tutorial
======
Related Software and Documents
+ Download GP ProEX Software for Proface GP4402WW Programming
+ Mitsubishi FR E700 Manual PDF Download (Password: plc247.com)
Please share the article to the community if you find it useful, please subscribe to Youtube channel and Website to read new articles
Thanks and Best Regards!