Hello everyone, HMI Delta DOP-107EV is a cheap but very good quality HMI. It supports most of the basic connectivity ports such as Ethernet, RS232, RS422/RS485. In addition to being able to connect to PLCs, it can also connect to devices via Modbus-RTU Communication.
Today plc247.com will guide you to use Delta HMI DOP-107EV to control Fuji Frenic Inverter via Modbus-RTU (Both devices have built-in RS485 port to support Modbus connection)

DOP-107EV & Fuji Frenic Inverter “Wiring Diagram”
+ Below is the connection diagram between HMI and VFD

FUJI Frenic Inverter Modbus Parameters Setting
In order for the Fuji Frenic Mini inverter to be controlled by Modbus-RTU, we need to set the following communication parameters
- H30: 3 (VFD Control via RS485 Port)
- Y01: 1 (Slave Address)
- Y02: 0
- Y03: 2
- Y04: 2 (9600bps)
- Y05: 0 (Data: 8bit)
- Y06: 1 (Parity Check: Even)
- Y07: 1 (Stop Bit: 1)
- Y10: 0 (Modbus-RTU Selection)
- Y99: 0
Fuji Frenic Inverter Modbus Registers Address
+ Functions Group Mapping

+ Registers for Control

+ Registers for Monitoring

- Frequency Setting Address = S(07H) + 05 = 705 (hex)
- Motor Control Address = S(07H) + 06 = 706 (hex)
+ Set Word “706” = 1 >>> Forward Run
= 2 >>> Reverse Run
= 0 >>> Stop Run
- Output Frequency Address = M(08H) + 09 = 809(hex)
Output Voltage Address = M(08H) + 12 = 80C(hex)
Delta HMI Modbus Programming
+ Communicaiton Configuration

+ Control Panel Design

+ Frequency Setting

+ Forward Run Command

+ Reverse Run Command

+ Stop Command

+ Frequency Output Read

+ Voltage Output Read

Project Video Tutorial
======
Related Software and Documents
+ Delta HMI Programming Software Download
+ FUJI Frenic Inverter Manual PDF Download
Password Extract: plc247.com
Thank you for reading the article, if you find it useful, please share the article to the community to let everyone know. Comment below the article if you need support, plc247.com will reply to you when I read the comments.
Best Regards!
Tłumaczenie tekstu za pomocą aparatu
Hello, do you have any guides with Bonfiglioli Active Cube inverters?
please comment via english