Hello, in previous posts plc247.com guided you to use HMI Proface to control many different devices using Modbus RTU Communication Standard.
Today plc247.com continues to guide you to control Siemens Sinamics V20 inverter with Proface GP4402WW (both devices have built-in RS485 port)
HMI Proface & Sinamics V20 “Wiring Diagram”
Siemens Sinamics V20 “Modbus RTU” Setting
In order for the inverter to be controlled by Modbus RTU, we need to set the following communication parameters
Registers Control Address
Note: GP4402WW HMI Address = “400001 (dec) + Device Address”
>>> Motor Control Address = 400001 + 99 = 400100
- Set Word 400100 = 1151 >>> Forward Run
= 3199 >>> Reverse Run
= 1150 >>> Stop
= 1278 >>> Reset
>>> Frequency Setting Address = 400001 + 100 = 400101
- Reference Setting = [0 to 16384] = [0 to 100%]
Registers Monitoring Address
>>> Motor Status Address = 400001 + 109 = 400110
Proface HMI Modbus Configuration
We need to set the communication parameters of the HMI Proface the same as those set in the Sinamics V20 VFD
HMI Programming
+ Control Panel
+ VFD Ready Status
+ VFD Running Status
+ VFD Alarm Status
+ VFD Reset Command
+ Frequency Set Command
+ Forward Start Command
+ Reverse Start Command
+ Stop Command
+ Frequency Output Monitoring
+ Current Output Monitoring
+ Voltage Output Monitoring
+ Speed Output Monitoring
Detailed Instruction Video
======
Related Software and Documents
+ HMI Proface Programming Software Download
+ Siemens Sinamics V20 Manual PDF Download (Password Extract: plc247.com)
Please comment and share the article if you find it useful. Subscribe to Youtube Channel and Website to read new articles of plc247.com
Thanks and Best Regards!
Sir Please tell
Set Word 400100 = 1151 >>
= 3199 >>> Reverse Run
= 1150 >>> Stop
= 1278 >>> Reset
Where it comes from 1151,3199,1150,1278,
Please help.