Keyence KV5500 “Modbus RTU” INVT Goodrive 20 VFD

Written by plc247.com

Hello everyone!
In the previous article, plc247.com guided people to use Weintek’s MT8071iE HMI to control the INVT GD20 inverter via Modbus RTU, today I will continue to guide you to use PLC Keyence to control it.

To be able to use Modbus RTU (RS485) I use PLC KV5500 in combination with Module KV-L21V to communicate with INVT inverter.

Keyence KV-L21V & INVT GD20 “Wiring Diagram”

If communication distance >50m or communication with multiple slave devices, need to use end resistor 120Ω

INVT GD20 Modbus Configurator

In order for the inverter to communicate with Modbus-RTU, we need to set the following communication parameters:

+ P00.01: 2 (Motor Control via RS485)

+ P00.06: 8 (Frequency Setting via RS485)

+ P00.09: 0 (A Frequency Selection)

+ P14.00: 1 (Slave Address)

+ P14.01: 3 (Baudrate-9600bps)

+ P14.02: 1 (8/1/E RTU)

+ P14.03: 5

+ P14.04: 0

Keyence KV5500 Programming

KV-L21V Modbus Configurator: Need Setting same VFD

+ Reset Data & Distribution Read/Write

+ Frequency Write Command

+ Motor Control Command

+ Read Data Response Command

Separate Data Output

Video Tutorial

======

Related Documents and Software:
+ KV-Studio for PLC KV5500 Programming
+ INVT Goodrive 20 Manual PDF (Password: plc247.com)

If you have any difficulties in connecting PLC Keyence to INVT GD20 via Modbus-RTU, please comment below the article. Please share this post if you find it useful.