Omron CP1H “Modbus RTU” INVT Goodrive 20 VFD

Written by plc247.com

Hello all of you. Today plc247.com will continue the series of instructions for controlling INVT-Goodrive 20 inverters using Modbus-RTU RS485 communication method.

And the PLC I choose today is the Omron CP1H PLC + CP1W CIF12 Module (or CP1W CIF11 is fine)

PLC Omron & INVT GD20 “Wiring Diagram”

If communicating with many slaves, or the communication distance is long, we need to add a 120Ω terminal resistor

INVT Goodrive 20 Modbus-RTU Configuration

In addition to the basic parameters of the inverter installed according to the motor, we need to configure additional communication parameters as follows:

  • P00.01 = 2 (Motor Control via RS485 Port)
  • P00.06 = 8 (Frequency Control via RS485 Port)
  • P00.09 = 0
  • P14.00 = 1 (Address No.1)
  • P14.01 = 3 (9600bps)
  • P14.02 = 1 (ModbusRTU 8/E/1)
  • P14.03 = 5
  • P14.04 = 0
Register for Control Motor

>>> Control Motor Address = 2000 (hex)

  • Set 2000(Hex) = 1 >>> Run Forward
  • Set 2000(Hex) = 2 >>> Run Reverse
  • Set 2000(Hex) = 5 >>> Stop

>>> Setting Frequency Address = 2001 (hex)

Register for Data Monitoring

>>> Output Frequency = 3000 (hex)

>>> Output Voltage = 3003 (hex)

>>> Output Current = 3004 (hex)

CP1H Communication Setting

We need to configure the communication parameters of the PLC to be the same as the INVT GD20

PLC Omron Programming

+ Reset Data when PLC Start

+ Transmission Distribution

+ Frequency Write Command

+ Motor Control Run Command

+ Read Data Response

+ Data Monitoring

Detailed Instruction Video

======

Documention Requirements

INVT Goodrive 20 Manual PDF (Password: plc247.com)

Please comment and share the article to the community if you find it useful.

Thanks and best regards!