Hello everyone, continuing the Series using HMI Samkoon SK-070HS to control various devices via Modbus-RTU communication protocol, today plc247.com continues to guide you to control Delta MS300 inverters.

Like the Samkoon HMI, the Delta MS300 inverter has a built-in RS485 port to support Modbus-RTU communication easily.

Samkoon HMI & Delta MS300 “Wiring Diagram”

Diagram of communication connection between Samkoon HMI and Delta MS300 inverter.

Delta MS300 “Modbus RTU” Configuration

In addition to the basic parameters of the inverter installed according to the motor (frequency, voltage, current …) then we need to install the following parameters:

  • P00.20 = 1 (Using Modbus Setting Frequency)
  • P00.21 = 2 (Using Modbus Control Motor)
  • P09.00 = 1 (Slave Address = 1)
  • P09.01 = 9.6 (Baudrate = 9600bps)
  • P09.02 = 3
  • P09.03 = 1.0 (Overtime Com. = 1.0s)
  • P09.04 = 14 ( Modbus-RTU 8/E/1 Selection)
Delta MS300 Modbus Registers Address

>>> Motor Control Address = 2000 (hex) = 8192 (dec)

  • Set Word 8192 = 18 (dec): Forward Run
  • Set Word 8192 = 34 (dec): Reverse Run
  • Set Word 8192 = 1 (dec): Stop

>>> Setting Frequency Address = 2001 (hex) = 8193 (dec)

+ Output Frequency Address = 2103 (hex) = 8451 (dec)

+ Output Current Address = 2104 (hex) = 8452 (dec)

+ Output Volatge Address = 2106 (hex) = 8454 (dec)

Samkoon HMI Modbus Parameters Setting

We need to set the communication parameters of HMI Samkoon according to the communication parameters installed for Delta MS300

HMI Programming

+ Control Panel

+ Setting Frequency

+ Forward Run

+ Reverse Run

+ Stop

+ Frequency Monitoring

+ Current Monitoring

+ Voltage Monitoring

Video Tutorial

======

Related Software and Documents

+ HMI Samkoon Software Free Download
+ Delta MS300 Manual PDF Download

Password Extract: plc247.com

If in the process of using Samkoon HMI to control Delta MS300 inverters through Modbus-RTU protocol, you need any support, please comment below the article, plc247.com will reply you as soon as possible.

Best Regards!

About the author

plc247.com

6 Comments

Leave a Comment

DMCA.com Protection Status