Hello everyone, automatic temperature control and storage is an increasingly necessary need for any factory. The Omron E5CC controller has Modbus Modbus-RTU support for this. That’s why today plc247.com guides you to use Samkoon HMI to connect and control it.
The HMI model used is Samkoon SK-070HS and uses the COM.0 port (Other HMI models are similar). You must pay attention to choose Model Omron E5CC with RS485 support, plc247.com uses Model “E5CC-RX2ASM-802”.

Samkoon HMI & Omron E5CC “Connection Diagram”
Note: If the communication distance is long, use terminal resistor

Omron E5CC Modbus Parameters Setting
To be able to control and monitor Omron E5CC via Modbus-RTU protocol, we need to set the following parameters:

Omron E5CC Registers Address

>>> Temperature Setting Address = 2103 (hex) = 8451 (dec)
>>> Temperature Monitoring Address = 2000 (hex) = 8192 (dec)
Samkoon HMI “Modbus RTU” Parameters Setting
Need to set the same communication parameters of HMI and Omron E5CC

Samkoon HMI Programming
+ Panel Design

+ E5CC No.1 SV (Set Value) Write

+ E5CC No.2 SV (Set Value) Write

+ E5CC No.1 PV (Present Value) Read

+ E5CC No.2 PV (Present Value) Read

Project Video Tutorial
======
Related Software and Documents
>>> Download Samkoon HMI Programming Software
>>> Omron E5CC Manual PDF Download
Password Extract: plc247.com
If you find the article interesting and useful, please comment and share the article to the community. Subscribe to Youtube channel and Website to read new articles of plc247.com
Thanks and Best Regards!