Hello everyone, today plc247.com would like to continue to share with you Series using PLC Siemens S7-1200 to control various devices. Today we will control the FUJI Frenic Series inverter
FUJI Frenic inverters are very diverse in types including: Mini, Eco, Multi, Mega
And today I use FUJI Frenic Mini to make this project
Connection Diagram
Using module S7-1200 combined with CB1241
FUJI FRENIC VFD Communication Configuration
In addition to the basic parameters of the Motor, we need to set the communication parameters as follows:
+ H30 = 3 (Run & Frequency Command via RS 485)
+ Y01 = 1 (Slave Station No.)
+ Y02 = 0
+ Y03 = 2.0 ( Timer Error Detect)
+ Y04 = 2 (9600bps)
+ Y05 = 0 (8bit)
+ Y06 = 1 (Even)
+ Y07 = 1 (1bit)
+ Y10 = 0 (Modbus-RTU)
+ Y99 = 0 (Folow H30 Funtion)
Register Address
This is the layout table of the register areas corresponding to the Hexa address of the inverter
The registers receive control commands from the PLC
>>> Frequency Reference = S (07hex) + 05 = 705 (hex) = 1797 (dec)
PLC Frequency Set Address = 40001 + 1797 = 41798 (dec)
>>> Operation Command = S (07hex) + 06 = 706 (hex) = 1798 (dec)
PLC Motor Control Address = 40001 + 1798 = 41799 (dec)
- Set 41799 = 1 >>> Run Forward
- Set 41799 = 2 >>> Run Revese
- Set 41799 = 0 >>> Stop
Data Feedback Registers
These are read-only registers about PLC
In this project I only read 2 Data included:
+ Output Frequency = M (08hex) + 09 = 809 (hex) = 2057 (dec)
>>> PLC Address = 40001 + 2057 = 42058 (Dec)
+ Output Voltage = M (08hex) + 12 = 80C (hex) = 2060 (dec)
>>> PLC Address = 40001 + 2060 = 42061 (dec)
Siemens S7-1200 Communication Configuration
S7 1200 CB1241 Configurator
Creating a Data Block for Modbus
PLC Programming
+ PLC Read/Write Distribution
+ PLC Communication Load
+ Frequency Setting
+ Motor Control Run
+ Frequency Output Read
+ Voltage Output Read
Video Tutorial
======
Documentation and Software:
- Fuji Frenic Series Modbus RS485 Manual PDF (Password Extract: plc247.com)
- Fuji Frenic Series Parameters Manual PDF
- TIA Portal V15.1 Professional Download
So plc247.com has finished guiding you to connect PLC Siemens and FUJI Frenic Mini inverter. If you have any questions, please comment below the article, I will answer you as soon as possible.