Hello friends!
The Hitachi NE-S1 inverter is an inverter from Japan that has been on the market for a long time and it supports all the basic connection types required of the inverter including Modbus-RTU communication.
Today plc247.com will guide you to use Samkoon SK-070HS HMI to control Hitachi NE-S1 inverter via Modbus-RTU protocol.

Samkoon HMI & Hitachi NE-S1 “Wiring Diagram”
Below is the RS485 communication wiring diagram between the Samkoon HMI and the Hitachi NES1 inverter.

Hitachi NE-S1 Modbus Parameters Setting
Below are the communication parameters and settings in the Project of Hitachi NES1 inverter:

+ “Modbus-RTU” select by SW5

Hitachi NE-S1 Modbus Registers Address

+ Frequency Setting Address = 1 (dec – Register)
+ VFD Start/Stop Address = 0 (dec – Coil)
+ VFD Direction Address = 1 (dec – Coil)
+ VFD Error Reset Address = 3 (dec – Coil)
+ VFD “Ready” Status Address = 16 (dec – Coil)
VFD “Running” Status Address = 18 (dec – Coil)
VFD “Alarm” Status Address = 23 (dec – Coil)
+ Output Frequency Address = 4097 (dec – Register)
Output Current Address = 4098 (dec – Register)
Output Voltage Address = 4112 (dec – Register)
Samkoon SK-070HS Modbus Configuration
“SKTOLL 7.0” Software Modbus Configuration

HMI Programming Example
+ Panel Design

+ VFD Ready Status

+ VFD Running Status

+ VFD Alarm Status

+ VFD Reset Alarm

+ Frequency Setting

+ Run Command

+ Stop Command

+ Direction Control

+ Frequency Output

+ Current Output

+ Voltage Output

Video Tutorial
======
References
+ Samkoon HMI Programming Software Download
+ Hitachi NE-S1 Manual PDF Download
Password Extract: plc247.com
If you find this article interesting and useful, please share it with the community. Subscribe to Youtube channel and Website to read new articles of plc247.com
Thanks and Best Regards!