The PowerFlex 525 inverter, with a power range of 0.4-22kW, is suitable for many different applications. The control module and the dynamics module are separable, allowing flexibility in project implementation.
Allen-Bradley PowerFlex 525 has built-in 1 Ethernet/IP port and 1 DSI (Serial) port, today plc247.com will guide you to use Kinco HMI to control it via Modbus-RTU protocol.
Samkoon HMI & PowerFlex 525 “Wiring Diagram”
+ RS485 communication connection diagram between HMI Samkoon SK-070HS and PowerFlex-525 inverter:
Allen-Bradley PowerFlex 525 Modbus Configuration
We need to set the following communication parameters to make PowerFlex 525 drive controllable by Modbus RTU protocol:
Allen-Bradley “PowerFlex 525” Modbus Registers Address
>>> VFD Control Address = 8192 (dec)
- Set Word 8192 = 18 (dec) >>> Run Forward
- Set Word 8192 = 34 (dec) >>> Run Reverse
- Set Word 8192 = 1 (dec) >>> Stop
= 8 (dec) >>> VFD Fault Reset
>>> Frequency Setting Address = 8193(dec)
>>> VFD Status Address = 8448 (dec)
+ Frequency Output Address = 8451 (dec)
+ Current Output Address = 8452 (dec)
+ Volatge Output Address = 8454 (dec)
Samkoon HMI Modbus Parameters Setting
We have set the communication parameters for the PowerFlex 525 inverter like that, the same settings for the Samkoon HMI
HMI Programming
+ Control Panel
+ VFD Ready Status
+ VFD Running Status
+ VFD Alarm Status
+ VFD Reset Command
+ Setting Frequency
+Run Forward Command
+ Run Reverse Command
+ Stop Command
+ Read Output Frequency
+ Read Output Current
+ Read Output Voltage