Hello friends!
Temperature monitoring and storage is now a must-have for any plant. The current thermostats all support Modbus-RTU communication, making it easy to store the temperature of the locations that need to be controlled. Omron E5CC is one of the popular thermostats on the market that supports this function.
Today plc247.com will guide you to use Mitsubishi GT2505-VTBD HMI to connect Omron E5CC Controller via Modbus-RTU (RS485) Communication Protocol.
Mitsubishi HMI & Omron E5CC “Wiring Diagram”
Note: If the communication distance is >50m, there is no need to use a 120Ω Terminal Resistor
Omron E5CC Modbus Parameters Setting
To be able to control and monitor Omron E5CC Controller through Modbus RTU, we need to set the following communication parameters:
Omron E5CC Registers Address Table
Note: Mitsubishi GOT2000 HMI Modbus RTU Address =
“Controller Address (Dec) + 400001“
>>> Set Temperature Address = 2103 (hex) + 1
= 8451 (dec) + 1 = 408452
>>> Temperature Monitoring Address = 2000 (hex) + 1
= 8192 (dec) + 1 = 408193
HMI Mitsubishi “Modbus RTU” Configuration
In order for the Mitsubishi GT2505 to be able to control the Omron E5CC, we need to configure the communication parameters of the HMi exactly the same of the E5CC Controller.
HMI Programming
+ Main Control Panel
+ E5CC No.1 Temperature Setting
+ E5CC No.2 Temperature Setting
+ E5CC No.1 Temperature Monitoring
+ E5CC No.2 Temperature Monitoring
Project Video Tutorial
======
Software References
+ Mitsubishi HMI Software Free Download
+ Omron E5CC Manual PDF Download
Password Extract: plc247.com
Please comment and share the article to the community if you find it interesting and useful. If you need support, please comment to plc247.com, I will reply to you as soon as I read the comments.
Best Regards!