Hi. In previous posts, plc247.com has instructed you to use a number of HMIs/PLCs to control Delta MS300 inverters via RS485 Modbus-RTU.
Today I would like to continue to guide you to use another common PLC to control it: Mitsubishi FX3U PLC combined with FX3U-485ADP-MB Module
Wiring Diagram
Setting DELTA MS300 VFD Parameters
If using Modbus-RTU to control the inverter, we set the communication parameters as follows:
- P00.20: 1 (Using Modbus Setting Frequency)
- P00.21: 2 (Using Modbus Control Motor)
- P09.00: 1 (Slave Address = 1)
- P09.01: 9.6 (Baudrate = 9600bps)
- P09.02: 0
- P09.03: 1.0 (Overtime Com. = 1.0s)
- P09.04: 14 ( Modbus-RTU 8/E/1 Selection)
Control Register Address
>>> Motor Control Address = 2000 (hex)
+ Set Word 2000 = 18 (dec): Forward Run
+ Set Word 2000 = 34 (dec): Reverse Run
+ Set Word 2000 = 1 (dec): Motor Stop
>>> Setting Frequency Address = 2001 (hex)
Register Monitoring Address
>>> Output Frequency Address = 2103 (hex)
>>> Output Current Address = 2104 (hex)
>>> Output Voltage Address = 2106 (hex)
Mitsubishi FX3U Programming
+ FX3U Ch2 Communication Setting
+ Read/Write Distribution
+ Setting Frequency
+ Motor Control Command
+ Data Monitoring Command
Project Tutorial Video
======
Documentation and supporting software:
Password Extract: plc247.com
Thank you, please comment and share the article if you find it useful.
Thanks and Best Regards!
Doesnt’ work on a FX3G, any solution or recommendation?
what module you using ?
I am using Module FX3U- 485ADP-MB with PLC Mitsubishi FX3G ,it is not working.
what happen for you
FX3G-485-BD-RJ
I think same fx3u