Hi. In the previous article, plc247.com showed you how to use PLC Delta to control many inverters of different brands. Today I will continue to guide you to use DVP-14SS2 PLC to control DELTA VFD-M Inverter.
Delta VFD-M inverter is a type of inverter used extremely commonly in factories because of its competitive price but extremely good quality, along with RS485 communication support built into the RJ11 port.
DVP 14SS2 & VFD-M Connection Diagram
You are looking to buy Jack RJ-11 (phone jack) to connect the VFD-M inverter.
VFD-M Parameters Setting
In order for VFD-M to be controlled by Modbus-RTU, we need to set the following communication parameters (I choose data type 9600/8/E/1)
+ Pr00: 03 (Control Frequency via RS485)
+ Pr01: 04 (Control Motor via RS485)
+ Pr88: 01 (Slave Address)
+ Pr89: 01 (9600bps)
+ Pr92: 04 (8bit/1bit/Even)
+ Pr157: 01 (Modbus-RTU)
Register For Control Motor
+ Motor Control Address = 2000 (Hex)
- Set 2000 (Hex) = 0000.0000.0001.0010 (Bin) = 18 (dec) >>> Forward Run
- Set 2000 (Hex) = 0000.0000.0010.0010 (Bin) = 34 (dec) >>> Reverse Run
- Set 2000 (Hex) = 0000.0000.0000.0001 (Bin) = 1 (dec) >>> Stop
+ Setting Frequency Address = 2001 (Hex)
Register For Data Monitoring
+ Output Frequency Address = 2103 (Hex)
+ Output Current Address = 2104 (Hex)
+ DC-BUS Voltage Address = 2105 (Hex)
+ Output Voltage Address = 2106 (Hex)
PLC Delta DVP-14SS2 Modbus Configuration
WPLSoft supports communication configuration as shown below:
After configuring the above table, the software will automatically create the program as below
PLC Programming
+ Read/Write Distribution
+ Write Frequency Data
+ Control Motor Command
+ Read Data Monitoring
Video Tutorials
======
Software & Documentation
+ Delta WPLSoft DVP PLC Programming Software
+ DELTA VFD-M Manual PDF Download (Password: plc247.com)
Please share the article to the community if you find it useful. Please comment below the article if you need assistance.