Continuing with the series of articles on how to use PLC Delta DVP to control the inverter via the Modbus-RTU RS485 communication standard, today plc247.com will guide you to control an inverter originating from Europe: Schneider ATV312 VFD.
Schneider’s ATV312 inverter has a built-in RJ45 port (Ethernet Port) that supports RS 485 . Communication.
Schneider ATV312 & DVP 14SS2 “Wiring Diagram”
Note: If communication distance > 50m, use end resistor 100/120-Ohm
Schneider ATV312 Modbus RTU Configuration
In addition to the basic parameters of the inverter (frequency, voltage, current, acceleration, deceleration…) we need to set the communication parameters as follows.
+ “COM” Menu
- Add = 1 (Slave No.1)
- tbr = 9.6 (baudrate)
- tF0 = 8E1 (Communication Config)
- tt0 = 3.0 (timer Com. error check)
+ “CtL” Menu
- LAC = L3
- Fr1 = Mdb (Modbus)
- Fr2 = Mdb
- CHCF = SEP
- Cd1 = Mdb
- Cd2 = Mdb
Register for Control
+ Motor Control Address = 8501 (decimal) = 2135 (hexa)
- Set Word 2135 (hex) = 128 >>> System Reset
= 6 >>> System Start
= 15 >>> Forward Run
= 2063 >>> Reverse Run
= 4111 >>> Stop
+ Frequency Setting Address = 8502 (decimal) = 2136 (hexa)
Register for Monitoring
+ Output Frequency Address = 3202 (decimal) = C82 (hexa)
+ Frequency Reference Address = C83 (hexa)
+ Output Current Address = C84 (hexa)
+ Motor Torque Address = C85 (hexa)
PLC DELTA DVP 14SS2 Comunication Configuration
You use WPLSoft software and choose the communication configuration as shown below:
The software will automatically create the program as below:
PLC Programming
+ Set Frequency Command
+ Control System & Motor
+ Read Data Response
Video Setup & Test Program
======
Software & Documents Reference:
- ATV312 Schneider Parameters Setting PDF
Communication Manual PDF
Modbus Address list PDF - WPLSoft for DELTA DVP PLC Programming
Password Extract: plc247.com
If you have any difficulties in using the DELTA PLC to control the Schnerder ATV312 inverter via Modbus-RTU, please comment below the article. plc247.com will reply to you as soon as possible.
Best Regards!
HOW TO KNOW WHAT VALUE SHOULD BE ENTER IN MODBUS REGISTER FOR A PARTICULAR COMMAND
Please read the documentation of ATV312
if I do have upto 6 schneider VFDs then what would be the changes into the PLC program?
available sir