Hello everyone!
In the previous post, plc247.com showed you how to use Delta PLC to control many types of inverters via Modbus RTU communication using the PLC’s RS485 communication port. Today I will show you how to use it to control Omron’s E5CC thermostat.
Omron E5CC is the most common type of temperature controller worldwide, and of course it supports Modbus-RTU. 1 PLC can control up to 32 E5CC with distance up to 1200m.
DVP 14SS2 & Omron E5CC ” Connection Diagram”
Below is a wiring diagram for Delta PLC and Omron E5CC, if the communication distance is > 50m, a 120.Ohm terminal resistor should be used.
Omron E5CC Modbus RTU Setting
plc247.com recommends that you configure according to the parameters below to be the most stable:
Register Modbus Address
Looking at the table above we can see:
+ SV (Set Value) Address = 2103 (Hex)
+ PV (Present Value) Address = 2000 (Hex)
DELTA DVP-14SS2 Modbus RTU Configuration
Communication configuration on WPLSoft Software
After selecting the communication parameters, the software will automatically create the following program (You can also programming the same program manually)
DVP 14SS2 Programming
+ Automatic Read/Write Distribution
+ Set Temperature Command (Set SV)
+ Read Temperature Present (PV)
Detailed Instruction Video
======
Required software and documention:
- Omron E5CC Manual PDF Download (password: plc247.com)
- WPLSoft V2.48 Software Download
If you have any problems in the process of connecting PLC Delta with Omron E5CC, please comment below the article, plc247.com will answer you as soon as I read it.
BR!
sir what is the password for the E5CC_PDF.rar? I can’t open the file?
password: plc4me.com sir
IAM TRYING TO GET THE MODBUS ADRESS OF THIRD PARTY DEVICE WHERE MODBUS ADRESS IN 40001 HOW EVER IF CONFIGURE IN DELTA GETTING AS INPUT ERROR.
H40001 IS NOT ACCEPTING CAN YO PLEASE HELP OUT
Click F1 on TIA Portal for read Manual sir
Please,explain me DTM instruction,sir.Thanks you.
Download DVP Manual have sir