PLC Guides Sensor Guides

DELTA DVP 14SS2 “Modbus RTU” Omron E5CC Tutorial

Written by plc247.com

Hello everyone!

In the previous post, plc247.com showed you how to use Delta PLC to control many types of inverters via Modbus RTU communication using the PLC’s RS485 communication port. Today I will show you how to use it to control Omron’s E5CC thermostat.

Omron E5CC is the most common type of temperature controller worldwide, and of course it supports Modbus-RTU. 1 PLC can control up to 32 E5CC with distance up to 1200m.

DVP 14SS2 & Omron E5CC ” Connection Diagram”

Below is a wiring diagram for Delta PLC and Omron E5CC, if the communication distance is > 50m, a 120.Ohm terminal resistor should be used.

Omron E5CC Modbus RTU Setting

plc247.com recommends that you configure according to the parameters below to be the most stable:

Register Modbus Address

Looking at the table above we can see:

+ SV (Set Value) Address = 2103 (Hex)

+ PV (Present Value) Address = 2000 (Hex)

DELTA DVP-14SS2 Modbus RTU Configuration

Communication configuration on WPLSoft Software

After selecting the communication parameters, the software will automatically create the following program (You can also programming the same program manually)

DVP 14SS2 Programming

+ Automatic Read/Write Distribution

+ Set Temperature Command (Set SV)

+ Read Temperature Present (PV)

Detailed Instruction Video

======

Required software and documention:

If you have any problems in the process of connecting PLC Delta with Omron E5CC, please comment below the article, plc247.com will answer you as soon as I read it.