Delta HMI “Modbus RTU” Autonics TK4S Tutorial

Written by plc247.com

Hello everyone, in the previous post plc247.com guided you to use Delta HMI to control and monitor Omron E5CC Temperature Controller through Modbus-RTU communication, today I will guide you to connect the same to Autonics TK4S.

You need to use Model TK4S with RS485 port support (In this project plc247.com uses Autonics TK4S-T4SN and HMI Delta DOP-107EV, other Delta HMIs with RS485 port have the same control).

DELTA DOP-107EV & Autonics TK4S “Wiring Diagram”

Note: Use a 120Ω Terminal Resistor if the communication distance is long.

Autonics TK4S Modbus Parameters Setting

– Below is a table of communication parameters that need to be set up for Autonics TK4S when using Modbus RTU

TK4S Controller >>> Press “Mode” >>> Choose “PAr.4”
  • AdrS = 1 (Modbus Slave)
  • bPS = 9.6 (9600bps)
  • Prty = EvEn (Parity check)
  • StP = 1 (Stop bit)
  • rSy.t = 20 (Response time)
Autonics TK4S Modbus Registers Address

>>> TK4S Set Temperature Address = 0 (Hex) / Funtion Code = “06”

>>> TK4S Temperature Monitoring = 3E8 (Hex) / Funtion Code = “04”

Delta HMI Modbus-RTU Configuration

We need to set the communication parameters of Delta DOP-107EV to be the same as those of Autonics TK4S before they can connection.

HMI Programming

+ Control Panel Design

+ TK4S No.1 Temperature Setting

+ TK4S No.2 Temperature Setting

+ TK4S No.1 Temperature Monitoring

+ TK4S No.2 Temperature Monitoring

Project Video Tutorial

======

Related Software and Documents

+ Delta DOP-107EV Software Free Download
+ Autonics TK4S Manual PDF Download