The Allen Bradley PowerFlex 525 is an extremely modern and powerful inverter. It supports many different control methods including Modbus RTU.
Today plc247.com will guide you to control PowerFlex 525 Inverter through Modbus RTU with HMI Proface GP4402WW (any HMI Proface with RS485 port will work)
PowerFlex 525 & GP4402WW “Connection Diagrams”

PowerFlex 525 Modbus RTU Configuration
In order for PowerFle 525 VFD to be controlled by Modbus RTU, in addition to the basic parameters (Frequency, current, voltage,…) we need to set the communication parameters as follows

Registers Address Table



Note: GP4402WW HMI Address = “400001 (dec) + Device Address”
+ Motor Control Address = 400001 + 8192 = 408193
- Set Word 408193 = 8 : Reset VFD
= 18 : Forward Run
= 34 : Reverse Run
= 1 : Stop
+ Frequency Reference Address = 400001 + 8193 = 408194
+ Output Frequency Address = 400001 + 8451 = 408452
+ Output Current Address = 400001 + 8452 = 408453
+ Output Voltage Address = 400001 + 8454 = 408455
HMI Proface Software Communication Setting
Need to set the same parameters as the installed PowerFlex 525

HMI Programming
+ Main Interface

+ Frequency Set Command

+ Forward Run Command

+ Reverse Run Command

+ Stop Command

+ Reset Alarm Command

+ Alarm Lamp

+ Output Frequency Monitoring

+ Output Current Monitoring

+ Output Voltage Monitoring

Detailed Video Tutorial
======
Related Software and Documents
+ HMI Proface Programming Software Download
+ Allen Bradley PowerFlex 525 PDF Download
Please share the article if you find it useful, if you have any questions or problems in the implementation of the project of connecting HMI GP4402WW with PowerFlex 525, please comment below the article.
Best Regards!