Hello everyone, Continuing the Series using Samkoon HMI to control various devices via Modbus-RTU protocol, today plc247.com will guide you to control Danfoss FC51 inverter.
Danfoss FC51 inverter has a built-in RS485 communication port, so we can directly connect the Samkoon HMI and the inverter easily.

Samkoon HMI & Danfoss FC51 “Connection Diagram”
Below is the RS485 communication connection diagram between Samkoon SK-070HS (other similar Samkoon HMI Models) and Danfoss FC51 inverter.

Danfoss FC51 Modbus Parameters Setting
Below are the Modbus-RTU communication parameters that need to be set up of the Danfoss FC51 inverter:

Danfoss FC51 Modbus Registers Address



>>> Control Word Address = 49999 (dec)
- Set Word 49999 = 1148 (dec) >>> Run Forward
= 33916 (dec) >>> Run Reverse
= 1084 (dec) >>> Stop
= 1212 (dec) >>> VFD Reset
>>> Set Frequency Address = 50009 (dec)
+ Reference Setting = 0 to 16384(dec) ~ (0 to 100%)
>>> Control Word Address = 50199 (dec)
>>> Output Frequency Address = 416129 (dec)
Samkoon HMI “Modbus RTU” Configuration
How did you install the Modbus parameters for the Danfoss FC51 inverter, the same settings for the Samkoon HMI

HMI Programming Example
+ Panel Design

+ Ready Status

+ Running Status

+ Alarm Status

+ Reset Command

+ Setting Frequency

+ Forward Run

+ Reverse Run

+ Stop Command

+ Output Frequency

Detailed Instruction Video
======
Related Software and Documents
+ Samkoon HMI Programming Software Download
+ Danfoss FC51 Manual PDF Download
Password Extract: plc247.com
If in the process of using HMI Samkoon to control Danfoss FC51 inverter you need any support, please comment below the article, plc247.com will reply to you as soon as I read the comments.
Thanks and Best Regards!