Hello everyone, automatic temperature control and storage is an increasingly necessary need for any factory. The Omron E5CC controller has Modbus Modbus-RTU support for this. That’s why today plc247.com guides you to use Samkoon HMI to connect and control it.
The HMI model used is Samkoon SK-070HS and uses the COM.0 port (Other HMI models are similar). You must pay attention to choose Model Omron E5CC with RS485 support, plc247.com uses Model “E5CC-RX2ASM-802”.

Samkoon HMI & Omron E5CC “Connection Diagram”
Note: If the communication distance is long, use terminal resistor

Omron E5CC Modbus Parameters Setting
To be able to control and monitor Omron E5CC via Modbus-RTU protocol, we need to set the following parameters:

Omron E5CC Registers Address

>>> Temperature Setting Address = 2103 (hex) = 8451 (dec)
>>> Temperature Monitoring Address = 2000 (hex) = 8192 (dec)
Samkoon HMI “Modbus RTU” Parameters Setting
Need to set the same communication parameters of HMI and Omron E5CC

Samkoon HMI Programming
+ Panel Design

+ E5CC No.1 SV (Set Value) Write

+ E5CC No.2 SV (Set Value) Write

+ E5CC No.1 PV (Present Value) Read

+ E5CC No.2 PV (Present Value) Read

Project Video Tutorial
======
Related Software and Documents
>>> Download Samkoon HMI Programming Software
>>> Omron E5CC Manual PDF Download
Password Extract: plc247.com
If you find the article interesting and useful, please comment and share the article to the community. Subscribe to Youtube channel and Website to read new articles of plc247.com