Mitsubishi FX5U “Modbus RTU” Inovance MD200 Tutorial

Written by plc247.com

Hello friends!
The Inovance MD200 inverter comes from China, the price is very cheap but the quality is quite good, so it is quite popular. In addition to supporting basic control types, it can also be controlled with CANLINK or Modbus RTU, today plc247.com will guide you to control it with Modbus RTU.

I use Mitsubishi FX5U PLC to control the Inovance MD200 inverter in the simplest and easiest way.

Mitsubishi FX5U & Inovance MD200 “Wiring Diagram”

+ Connection Diagram

Inovance MD200 Modbus Configuration

In order for the Mitsubishi FX5U PLC to control the Inovance inverter using the Modbus RTU protocol, we need to set the following communication parameters:

+ VFD Control Address = 2000 (hex)

  • Set Word “2000” = 1 >>> Forward Run
  • Set Word “2000” = 2 >>> Reverse Run
  • Set Word “2000” = 6 >>> Stop

+ Set Frequency Address = 1000 (hex)
>>> Frequency Reference = (0 to 10000 dec) ~ (0 to VFD Max Frequency)

  • Output Frequency Address = 1001 (hex)
    Output Voltage Address = 1003 (hex)
    Output Current Address = 1004 (hex)

PLC Mitsubishi “Modbus RTU” Configuration

How have we set up the communication parameters for the inverter, the settings for the Mitsubishi FX5U PLC are exactly the same.

PLC Programming

+ Reset Control when PLC Start

+ Read/Write Distribution

+ VFD Control Command

+ Read Data Output

Project Video Tutorial

======