LS iG5A VFD “Modbus RTU” via Modbus Poll

Written by plc247.com

LS iG5A inverter is a type of Korean inverter with good quality with reasonable price. Today plc247.com will guide you to use PC to control it via Modbus-RTU RS485 communication standard.

We need to prepare the software “Modbus Poll” (Download link at the bottom of the article, capacity 3MB) and USB to RS485 Cable

PC & LS iG5A Modbus RTU Wiring Diagram

LS iG5A VFD Configuration

Below is the communication parameter table of the LS iG5A

You can configure the following according to the project:

  • Drv = 3
  • Frq = 7
  • I59 = 0
  • I60 = 1
  • I61 = 3
  • I62 = 0
  • I65 = 2

LS iG5A Modbus Register Address List

Note: For LS iG5A VFD Series

Control Address = “Register Address – 1”

>>> Motor Control Address = 6 – 1 = 5

  • Set Word 5 = 2 >>> Forward Run
    = 4 >>> Reverse Run
    = 0 >>> Motor Stop

>>> Frequency Setting Address = 5 – 1 = 4

>>> Output Current Address = 9 – 1 = 8
Frequency Address = A – 1 = 9
Voltage Address = B – 1 = A (hex)

“Modbus Poll” Programming

+ Motor Control Command

+ Setting Frequency Command

+ Read Data Response

Video Tutorial

======

Reference

+ LS iG5A VFD Manual PDF Download (Password: plc247.com)

+ Modbus poll Software Download

If you have any questions, please comment below the article. Please share the article if you find it useful.

Thanks and Best Regards!