Schneider Electric’s Proface HMI is one of the best quality but cheap HMIs, so it’s widely used in machines around the world. HMI Proface fully supports industrial communication protocols such as Ethernet, RS232, RS422/485…
Today plc247.com will guide you to use HMI Proface GP4402WW to control Omron E5CC Controller via Modbus RTU RS485
GP4402WW & Omron E5CC “Diagram Connection”
Omron E5CC Communication Setting
E5CC includes the following parameters as the table below, plc247.com recommends that you install the same as this project (see the video below the article for details)
Registers Address Table
Note: GP4402WW HMI Address = “400001 (dec) + Device Address”
>>> Set Temperature Address (SV) = 400001 (dec) + 2103 (hex)
= 400001 (dec) + 8451 (dec) = 408452 (dec)
>>> Read Present Temperature Address (PV) = 400001 (dec) + 2000 (hex)
= 400001 (dec) + 8192 (dec)
= 408193 (dec)
Proface GP4402WW Modbus RTU Configuration
We need to configure the same communication parameters as Omron E5CC Controller
HMI Programming
+ Control Panel Design
+ E5CC.1 Temperature Setting
+ E5CC.2 Temperature Setting
+ E5CC.1 Temperature Present Read
+ E5CC.2 Temperature Present Read
Detailed Video Instructions
======
Related Software and Documents
>>> Download GP ProEX for Proface HMI Programming Software
>>> Omron E5CC Manual PDF Download (Password: plc247.com)
If you have any difficulties in implementing the project of connecting GP4402WW with Omron E5CC, please comment below the article, plc247.com will answer you as soon as possible.