The Powerflex 525 inverter is a series of Rockwell’s 520 inverter series. The Powerflex 520 inverter series was born to meet Rockwell’s Logix platform in common applications requiring inverters, it has built-in Ethernet/IP and RS485 ports which is convenient for controlling and monitoring the inverter by communication.
So today plc247.com will write a tutorial on how to use HMI Delta DOP-107EV (other models with RS485 ports are similar) to control Allen-Bradley PowerFlex525 through “Modbus RTU” RS485

Delta DOP-107EV & PowerFlex525 “Wiring Diagram”
Note: Use twisted pair cable and Terminal resistor 120Ω if Communication distance is long

PowerFlex 525 Modbus Parameters Setting
In order for the Allen-Bradley PowerFlex 525 to be controlled and monitored by Modbus-RTU, we need to set the following communication parameters

PowerFlex525 Inverter Modbus Registers Address
Registers for Control


>>> Motor Control Address = 2000 (Hexa)
- Set Word 2000 = 18 (dec) >>> Run Forward
- Set Word 2000 = 34 (dec) >>> Run Reverse
- Set Word 2000 = 1 (dec) >>> Stop
= 8 (dec) >>> VFD Fault Reset
>>> Frequency Setting Address = 2001 (Hexa)
Registers for Monitoring


>>> VFD Status Address = 2100 (Hexa)
+ Output Frequency Address = 2103 (Hexa)
+ Output Current Address = 2104 (Hexa)
+ Output Voltage Address = 2106 (Hexa)
HMI Delta Modbus-RTU Configuration
We need to set the communication parameters of the HMI DOP-107EV to be the same as those installed for the PowerFlex 525 Inverter before they can be connected and control

HMI Programming
+ Control Panel Design

+ VFD Ready

+ Frequency Reference

+ Forward Run

+ Reverse Run

+ Stop Command

+ VFD Reset

+ Frequency Monitoring

+ Current Monitoring

+ Voltage Monitoring

Detailed Instruction Video
======
Software and Documents
+ Delta HMI Software Free Download
+ Allen-Bradley PowerFlex 525 Manual PDF Download
(Password Extract: plc247.com)
Please comment and share the article to the community if you find it useful. Subscribe to Youtube channel and Website to read new articles of plc247.com
Thanks and Best Regards!