Delta MS300 inverter is a new type of inverter launched to replace old inverters such as VFD-M, VFD-L. It also has a built-in RS485 communication port for Modbus-RTU Control.
Today plc247.com will guide you to use HMI Proface GP4402WW to control and monitor Delta MS300 VFD through Modbus RTU Communication Standard.
Delta MS300 & GP4402WW “Wiring Diagram”

Delta MS300 Modbus RTU Configuration
In addition to the basic parameters of the inverter (Frequency, voltage, current, Acc/Dec,…) then we need to set the communication parameters as follows
+ P00.20 = 1 (Modbus-RTU Control Frequency)
+ P00.21 = 2 (Modbus-RTU Control Motor)
+ P09.00 = 1 (Address Slave = 1)
+ P09.01 = 9.6 (9600bps)
+ P09.02 = 0
+ P09.03 = 1.0 (Time Detect Err = 1.0s)
+ P09.04 = 14 (Modbus-RTU Slection 8bit / stop bit = 1/ Even)
Registers Address Table


Note: GP4402WW HMI Address = “400001 (dec) + Device Address”
+ Control Address = 400001(dec) + 2000(hex) = 400001 + 8192 = 408193
- Set Word 408193 = 18 >>> Forward Run
= 34 >>> Reverse Run
= 1 >>> Stop
+ Frequency Set Address = 400001(dec) + 2001(hex) = 400001 + 8194 = 408194
+ Frequency Output Address = 400001(dec) + 2103(hex) = 400001 + 8451 = 408452
+ Current Output Address = 400001(dec) + 2104(hex) = 400001 + 8452 = 408453
+ Voltage Output Address = 400001(dec) + 2106(hex) = 400001 + 8454 = 408455
HMI Proface GP4402WW Communication Setting
You need to set the same communication parameters as the Inverter parameters

HMI Programming
+ Main Control Panel

+ Frequency Setting

+ Motor Forward Run

+ Motor Reverse Run

+ Motor Stop

+ Frequency Output

+ Current Output

+ Voltage Output

Detailed Instruction Video
======
Related Software and Documents
+ HMI Proface Programming Software Download
+ Delta MS300 VFD Manual PDF Download (password: plc247.com)
Please share the article to the community if you find it useful, if there is any difficulty in connecting GP4402WW with MS300 VFD, please comment below the article, plc247.com will reply you as soon as possible
Best Regards!