Hello friends!
Continuing the series of articles using Mitsubishi QJ71C24N to control different devices through the Modbus-RTU communication protocol, today plc247.com continues to guide you to control the PowerFlex 525 inverter.
The Allen-Bradley PowerFlex 525 inverter has a built-in RS485 communication port that makes it easy to connect to it from the QJ71C24N Module.

QJ71C24N & PowerFlex 525 “Connection Diagram”
Below is a diagram of Modbus RS485 communication connection between QJ71C24N and PowerFlex 525

PowerFlex 525 “Modbus RTU” Parameters Setting
To be able to control and monitor the PowerFlex 525 through the Modbus-RTU protocol, we need to set the following parameters:

PowerFlex525 Modbus Registers Address



+ VFD Control Address = 2000 (Hexa)
- Set Word 2000 = 18 >>> Motor Forward Start
= 34 >>> Motor Reverse Start
= 1 >>> Stop
= 8 >>> VFD Fault Reset
+ Frequency Reference Address = 2001 (Hexa)
- Frequency Command Address = 2102 (Hexa)
- Output Frequency Address = 2103 (Hexa)
- Output Current Address = 2104 (Hexa)
- DC-BUS Voltage Address = 2105 (Hexa)
- Output Voltage Address = 2106 (Hexa)
Mitsubishi QJ71C24N “Modbus RTU” Configuration
Here are the basic configuration steps to set parameters for Mitsubishi QJ71C24N
+ Step 1: Create New Project

+ Step 2: I/O Configuration

+ Step 3: Channel.2 Parameters Setting

+ Step 4: Sent Parameters to Module QJ71C24N

+ Step 5: Disable “Echoback”
- Set G450 = 1 (Disable Echoback)

QJ71C24N & PowerFlex 525 “Protocols Setting”
>>> Protocol No.1: Func = 06 / “Write Single Registers”
- Slave Address = D100
- Register Adress = D101
- Register Value = D110
- “Comm. Error” = D300
>>> Protocol No.2: Func = 03 / “Read Holding Registers”
- Slave Address = D200
- Starting Address = D201
- Quantity of Registers = D202
- Registers Value Response = D210 “From D210…D335 depending on the number of Registers (D202) to read”
- “Comm. Error” = D300






HMI Programming
+ Error Clear & Disable Echoback

+ Communication Distribution

+ Frequency Setting Command

+ VFD Control Command

+ Data Output Monitoring

+ HMI Control Panel

Project Video Tutorial
======
References
+ Download Mitsubishi GX-Works 2 Full Software
+ HMI Weintek & Mitsubishi Q03UDV “Connection Tutorial”
+ Download Allen-Bradley PowerFlex 525 Manual PDF
Password Extract: plc247.com
Please comment and share the article to the community if you find it interesting and useful, then please share it with the community for everyone to know. Subscribe to Youtube channel and Website to read new articles of plc247.com
Thanks and Best Regards!