Inovance inverter is a versatile mini inverter series, widely applied in the market. The outstanding advantage of this line is good quality, durable and stable operation. MD200 stands out for its competitive price in the market. This is also the product that is preferred by most customers because it ensures quality criteria and brings high economic efficiency.
Today plc247.com will use the Keyence PLC in combination with the KV-L21V Module to control the Inovance MD200 inverter through the Modbus RTU communication protocol.

PLC Keyence & Inovance MD200 “Wiring Diagram”
We need to choose the Inovance MD200 inverter model that supports RS485 port and connect according to the following diagram:

Inovance MD200 “Modbus RTU” Configuration
Below are the communication parameters to be installed for the Inovance MD200 inverter:

Inovance MD200 Modbus Registers Address


+ Motor Control Address = 2000 (hex)
- Set Word 2000 = 1 >>> Forward Run
- Set Word 2000 = 2 >>> Reverse Run
- Set Word 2000 = 6 >>> Stop
+ Frequency Setting Address = 1000 (hex)
>>> Frequency Reference = (0 to 10000 dec) ~ (0 to VFD Max Frequency Setting)
- Output Frequency Address = 1001 (hex)
- DC-BUS Voltage Address = 1002 (hex)
- Output Voltage Address = 1003 (hex)
- Output Current Address = 1004 (hex)
Keyence KV-L21V “Modbus RTU” Parameters Setting
We need to set the Modbus communication parameters for the Keyence KV-L21V Module the same as those installed for the MD200 inverter.

PLC Keyence Modbus Example
+ Transmission Distribution

+ Frequency Setting Command

+ VFD Control Command

+ Read Data Response

Project Video Tutorial
======
Related Software and Documents
+ Keyence KV-Studio Version 11 Download
+ Inovance MD200 Manual PDF Download
Password Extract: plc247.com
Please comment and share the article to the community if you find it interesting and useful. Subscribe to Youtube channel and Website to read new articles of website plc247.com
Thanks and Best Regards!