Hello friends. Delta VFD-M inverter is a type of inverter commonly used on the market (now discontinued), it fully supports the basic control connections of an inverter, including communication interface “Modbus-RTU” Communication Protocol.
Today plc247.com will guide you to use HMI Samkoon SK-070HS to control it simply and easily without connecting many wires.

Samkoon HMI & Delta VFD-M “Wiring Diagram”
RS485 communication connection diagram between Samkoon HMI and Delta VFD-M inverter (Delta VFD-M RS485 port is RJ11 port (desktop phone port).

Delta VFD-M Modbus Parameters Setting
Below are the Modbus-RTU communication parameters of Delta VFD-M inverter:
- P00 = “03” (Frequency Set by RS485)
- P01 = “04” ( Control by RS485)
- P88 = “01” (Slave Address)
- P89 = “01” (Baudrate 9600bps)
- P92 = “04” ( Mode 8/1/Even)
- P157 = “01” (Modbus-RTU Selection)
Delta VFD-M Modbus Registers Address


>>> VFD Control Address = 2000 (hex) = 8192 (dec)
+ Set Word 8192 = 18 (dec): Forward Run
+ Set Word 8192 = 34 (dec): Reverse Run
+ Set Word 8192 = 1 (dec): Stop
>>> Frequency Set Address = 2001 (hex) = 8194 (dec)
>>> Output Frequency Address = 2103 (hex) = 8451 (dec)
>>> Output Current Address = 2104 (hex) = 8452 (dec)
>>> Output Voltage Address = 2106 (hex) = 8454 (dec)
Samkoon HMI Modbus Configuration
We need to set the communication parameters of Delta VFD-M and HMI Samkoon the same:

HMI Programming Example
+ Main Page Design

+ Setting Frequency

+ Forward Run

+ Reverse Run

+ Stop

+ Output Frequency

+ Output Current

+ Output Voltage

Project Video Tutorial
======
Related Software and Documents
+ Download HMI Samkoon Programming Software
+ Delta VFD-M Manual PDF Download