Hello friends. Sinamics V20 is a small general-purpose inverter from Siemens. It can be controlled by various methods including Modbus RTU.
Today plc247.com will guide you to control Siemens Sinamics V20 easily through Modbus Poll software. We need to prepare the “USB to RS485” cable
Sinamics V20 & Computer “Connection Diagram”
Siemens Sinamics V20 Modbus RTU Configuration
To be able to control Siemens Sinamics V20 with “Modbus RTU” we need to configure the following communication parameters
Register for Control Address
+ VFD Control Address = 99
- Set Word 99 = 1151 >>> Forward Run
= 3199 >>> Reverse Run - Set Word 99 = 1150 >>> Stop
- Set Word 99 = 1278 >>> VFD Reset
+ Frequency Reference Address = 100
Register for Monitoring Address
+ Frequency Output Address = 23
+ Speed Output Address = 24
+ Current Output Address = 25
Modbus Poll Programming
+ Frequency Setting
+ VFD Control Command
+ Data Monitoring
Project Video Tutorial
======
Related Software and Documents
+ Modbus Poll Software Free Download
+ Siemens Sinamics V20 Manual PDF Download
Password Extract: plc247.com
If you have any questions, need help connecting Modbus Poll software with Siemens Sinamics V20, please comment below the article.