Drives Inverters Guides PLC Guides

Siemens S7-200 “Modbus RTU” LS iG5A Inverter

Written by plc247.com

Hello friends!
Continuing the series of articles on how to use Siemens PLC to control different devices through Modbus RTU, today plc247.com will guide you to control the LS iG5A Inverter.

Both of these devices have built-in RS485 communication, plc247.com will guide you to connect and program so they can connect to each other in the simplest and easiest way.

Siemens S7-200 & LS iG5A “Connection Diagram”

Below is the RS485 communication connection diagram between Siemens S7-200 and LS iG5A Inverter.

LS iG5A “Modbus RTU” Parameters Setting

To be able to control the LS iG5A inverter with Modbus-RTU, in addition to the basic parameters of the inverter (frequency, voltage, current …) we need to install the following communication parameters:

plc247.com recommends that you install the following for stable communication:

  • Drv = 3
  • Frq = 7
  • I59 = 0 (Choose Modbus-RTU)
  • I60 = 1 (Slave No.1)
  • I61 = 3 (baudrate 9600bps)
  • I62 = 0
  • I65 = 2 (Even/1bit)
LS iG5A Registers Address Table
Note: Siemens S7-200 & LS iG5A Holding Registers Address =
“VFD Address (Dec) + 40000

+ Frequency Setting Address = 5 + 40000 = 40005 (dec)

+ VFD Control Address = 6 + 40000 = 40006 (dec)

  • Set Word “40006” = 2 >>> Run Forward
  • Set Word “40006” = 4 >>> Run Reverse
  • Set Word “40006” = 0 >>> Stop

+ Current Output Address = 9 + 40000 = 40009 (dec)
+ Frequency Output Address = A (hex) + 40000 = 10 (dec) + 40000 = 40010 (dec)
+ Voltage Output Address = B (hex) + 40000 = 11 (dec) + 40000 = 40011 (dec)

PLC Programming Example

+ Read/Write Distribution

+ Modbus Parameters Configuration

+ Frequency Setting Write

+ VFD Control Run

+ Read Data Monitoring

Project Video Tutorial

======

Related Software and Documents
+ Siemens S7-200 Programming Software Download
+ LS iG5A VFD Manual PDF Download

Password Extract: plc247.com

If in the process of using the Siemens S7-200 PLC to control the LS iG5A inverter through Modbus-RTU you need any support, please comment below the article, plc247.com will reply you as soon as I read comments.

Thanks and Best Regards!

About the author

plc247.com

Leave a Comment

DMCA.com Protection Status