Drives Inverters Guides PLC Guides

PLC Keyence “Modbus RTU” LS iG5A VFD Tutorial

Written by plc247.com

Continuing with the series of articles on how to control LS iG5A VFD via Modbus-RTU (RS485) communication standard, today plc247.com would like to continue to guide you to use PLC Keyence to control

We can use any Keyence PLC of KV-Series in combination with Module KV-L21/21V to connect.

Keyence KV-L21V & LS iG5A VFD Connection Diagram

LS iG5A Configurator

In addition to the basic parameters for the motor installation, we need to set the communication parameters according to the following table

+ Drv = 3

+ Frq = 7

+ I59 = 0

+ I60 = 1

+ I61 = 3

+ I62 = 0

+ I65 = 2

Modbus Regigter Address

Note: PLC Register Address = “Address – 1”

PLC Keyence Modbus RTU Configurator

We need to set the same parameter as the inverter

KV5500 PLC Programming

+ Reset registers when PLC starts running & Control Read/Write

+ Frequency Write Command

+ Control Run Command

+ Read Data Command

+ Read Data Reponse

Video Installing and Running the Program

======

Required documents and software:

+ KV Studio for PLC Keyence Programming

+ LS iG5A VFD Manual PDF Download (Password Extract: plc247.com)

If you need any support, please comment below the article, plc247.com will reply to you as soon as possible.

Best Regards!

About the author

plc247.com

Leave a Comment

DMCA.com Protection Status