Hello friends, in previous posts plc247.com guided you to use LabView software to Temperature Controller as well as many different types of VFD.
Today plc247.com continues to guide you to use LabView to control FUJI Frenic Series Inverter.
Computer & Fuji Frenic VFD “Wiring Diagram”
Fuji Frenic Modbus RTU Configuration
In order for the Fuji Frenic inverter to be controlled by Modbus RTU through the RS485 port, we need to set the following parameters:
+ H30: 3 (Run & Frequency Command via RS 485)
+ Y01: 1 (Slave Station No.)
+ Y02: 0
+ Y03: 2.0 ( Timer Error Detect)
+ Y04: 2 (9600bps)
+ Y05: 0 (8bit)
+ Y06: 1 (Even)
+ Y07: 1 (1bit)
+ Y10: 0 (Modbus-RTU)
+ Y99: 0 (Folow H30 Funtion)
Registers Table Address
Table of hexa addresses corresponding to Parameter Groups
Registers for Control
>>> Frequency Reference Address = S (07) + 05 = 705 (hex) = 1797 (dec)
>>> Motor Control Address = S (07) + 06 = 706 (hex) = 1798 (dec)
+ Set Word 1798 = 1 >>> Forward Run
= 2 >>> Reverse Run
= 0 >>> Stop
Registers for Monitoring
+ Output Frequency Address = M (08) + 09 = 809 (hex) = 2057 (dec)
LabView Programming
+ Front Panel
+ Block Diagram
Video Tutorial
======
Required Documentation
+ Fuji Frenic Parameters Setting Manual PDF
Fuji Frenic Series Modbus RS485 Manual PDF
Password Extract: plc247.com
Please comment and share the article if you find it useful. If you have any difficulty, please comment below the article, plc247.com will reply to you as soon as I read it.
Best Regards!
Dear Sir,
I hope you are well. I urge you to take a video lab view with the Mitsubishi FR F800 series.
search on my website have FR E700 same sir
hello,
Can you please make a video for Benshaw RSi SG Series drives, I will deeply appreciate it.
Sorry, I don’t have this item
what a version of the modbus package ?
Ang Version sir