Schneider Altivar 312 Inverter, ATV312 is a family of inverters developed by electric-schneider with powerful features with frequency range from 0 to 500Hz, capacity 0.18 to 15Kw with many functions such as: Motor thermal protection, auto-start function, load-speed auto-start function, reversing function, braking function, remote control connection function.
Today plc247.com will write a tutorial for you to use HMI Proface GP4402WW to control Schneider ATV312 through Modbus RTU RS485 Communication.
GP4402WW & Schnerider ATV312 “Wiring Diagram”

Schneider ATV312 VFD Communication Setting
In order for the inverter to be controlled by Modbus RTU, we need to set the communication parameters as follows:
- “CON” Menu
+ Add: 1 (Slave Address= 1)
+ tbr: 9.6 (Baudrate = 9600bps)
+ tF0: 8E1
+ tt0: 3.0 (Comm. timer check Error)
- “CtL” Menu
+ LAC: L3
+ Fr1: Mdb (Modbus)
+ Fr2: Mbd
+ CHCF: SEP
+ Cd1: Mbd
+Cd2: Mbd
Register Address Table


Note: GP4402WW HMI Address = “400001 (dec) + Device Address”
>>> Motor Control Address = 400001+ 8501 = 408502
+ Set Word 408502 = 128 : VFD Fault Reset
= 6 : VFD System Start
= 15 : Motor Forward Run
= 2063 : Motor Reverse Run
= 4111 : Stop
>>> Frequency Reference Address = 400001 + 8502 = 408053
>>> Output Frequency Address = 400001 + 3202 = 403203
>>> Output Current Address = 400001 + 3204 = 403205
Proface HMI Modbus RTU Configuration
We need to set the communication parameters the same as those set in the Schneider ATV312

GP4402WW HMI Programming
+ Control Panel

+ Frequency Setting

+ Error Lamp

+ Ready Lamp

+ VFD Reset Error

+ VFD Start System

+ Fordward Run

+ Reverse Run

+ Stop

+ Output Frequency

+ Output Current

Project Video Tutorial
======
Related Software and Documents
- Proface GP4402WW Programming Software Download
- Schneider Altivar 312 Manual PDF Download (Password Extract: plc247.com)
Please share the article to the community if you find it useful. Subscribe to Youtube channel and Website to read new articles.