Delta VFD-M is a type of inverter commonly used in small and medium-sized machines, now it is no longer produced and replaced by newer Models. However in many cases we still have to work with them.
Today plc247.com will guide you to use HMI Proface GP4402WW to connect to Delta VFD M via built-in RS485 “Modbus RTU”
GP4402WW & Delta VFD-M “Connection Diagram”

Delta VFD-M Communication Setting

Note: GP4402WW HMI Address = “400001 (dec) + Device Address”
Register for Control

>>> Motor Control Address = 400001 (dec) + 2000 (hex)
= 400001 (dec) + 8192 (dec) = 408193
+ Set Word 408193 = 18 >>> Forward Run
= 34 >>> Reverse Run
= 1 >>> Stop
>>> Frequency Reference Address = 400001 (dec) + 2001 (hex)
= 400001 (dec) + 8193 (hex) = 408194
Register for Monitoring

>>> Output Frequency Address = 400001 (dec) + 2103 (hex)
= 400001 (dec) + 8451 (dec) = 408452
>>> Output Current Address = 408453
>>> Output Voltage Address = 408455
GP-ProEX Proface Software Configuration
You configure the communication parameters corresponding to those installed in Delta VFD-M

GP4402WW HMI Programming
+ Control Panel Design

+ Frequency Reference

+ Forward Command

+ Reverse Command

+ Stop Command

+ Output Frequency

+ Output Current

+ Output Voltage

Project Video Tutorial
======
Related Software and Documents
- HMI Proface Programming Software Download
- Delta VFD-M Manual PDF Download (Password Extract: plc247.com)
If you have any difficulties in using HMI GP4402WW to control Delta VFD-M inverters, please comment below the article, plc247.com will reply to you as soon as I read the comments.
Best Regards!