Hello, Siemens PLC S7-1200 and Danfoss-FC302 inverter are two devices commonly used in many machines around the world, especially standalone machines.
Today plc247.com will guide you to use PLC S7-1200 to connect and control Danfoss FC302 via Modbus RTU (RS485).
Siemens S7-1200 & Danfoss FC51 “Wiring Diagram”
With S7-1200 we need to use more RS485 Module: S7-1200 CB1241 (or S7-1200 CM1241), and with Danfoss FC51 inverter, it has a built-in RS485 Port.

Danfoss FC51 Modbus RTU Configuration
To be able to control Danfoss FC51 with Modbus RTU, we need to configure the following parameters

Danfoss FC51 Registers for Control

Note: S7-1200 Modbus Address
= “VFD Address (dec) + 400001”
>>> VFD Control Address = 49999 + 400001 = 450000
- Set Register 450000 = 1148 (dec) >>> Run Forward
= 33916 (dec) >>> Run Reverse - Set Register 450000 = 1084 (dec) >>> Stop
- Set Register 450000 = 1212 (dec) >>> VFD Reset
>>> VFD Frequency Setting Address = 50009 + 400001 = 450010
- Speed Reference = 0 to 16384(dec) ~ (0 to 100%)
Danfoss FC51 Registers for Monitoring

- Output Voltage Address = 416120 (dec)
- Output Frequency Address = 416130 (dec)
- Output Current Address = 416140 (dec)
Siemens S7-1200 Modbus RTU Setting
We need to set the communication parameters of S7-1200 the same as Danfoss FC51
+ S7-1200 RS485 Parameters Setting

+ Data Block Create

S7-1200 Modbus RTU Example
+ Read and Write Distribution

+ VFD Frequency Setting

+ VFD Control Command

+ Read Ouput Voltage

+ Read Output Frequency

+ Read Output Current

Project Video Tutorial
======
Related Software and Documents
+ Download Siemens S7-1200 Programming Software
+ Danfoss FC51 Manual PDF Download
Password Extract: plc247.com
If in the process of connecting S7-1200 with Danfoss FC51 you have any questions, please comment below the article, plc247.com will answer you as soon as I read the comments.
Best Regards!

How setting was change if I use 19 Inveter
only change slave address
Hello i have 43 number of vfd and you are only using clock hz for one vfd how should i manage the clock hz for multiples number of vfd can i create different counter clock hz for different vfds?
43 VFDs can also control, using two RS485 Modules
How do you know register adresses?
need read danfoss fc51 manual pdf
Please how did you know the control word for run.
How did you calculate it
You need read Danfoss FC51 Manual
hi, thanks for you support. The link “+ Download Siemens S7-1200 Programming Software” is not wrking, thanks from Chile.
ok sir, i will fixed link
Hello, I can not open the link “+ Download Siemens S7-1200 Programming Software”, please help.
https://plc247.com/download-tia-portal-v18-full-video-installation/
Can you please make a video and an explanation of S7-1200 Modbus RTU Example with an ABB vsd please and also how to select setting and enabling RTU communication on ABB VSD part
ok waiting me sir