Hello friends!
Continuing the Series using different PLCs and HMIs to control Inovance MD200 inverters, today plc247.com continues to guide you to use Siemens PLCs to control it.
The PLC model I use is Siemens S7-1200 combined with Module S-1200 CB1241 (can also use CM1241) to connect to RS485 port of Inovance MD200.

PLC Siemens & Inovance MD200 “Wiring Diagram”
Below is the RS485 communication connection diagram between PLC S7-1200 and Inovance MD200.

Inovance MD200 Modbus Configuration
In addition to the basic parameters of the inverter installed according to the motor (frequency, voltage, current …) in order for the inverter to be controlled and monitored by Modbus RTU, we need to install additional following parameters

Inovance MD200 Registers Address


Note: Siemens S7-1200 Holding Registers Address =
“VFD Address (Dec) + 40001“
>>> VFD Control Address = 2000 (hex) = 8192 (dec) + 40001 = 48193 (dec)
- Set Word 48193 = 1 >>> Forward Run
- Set Word 48193 = 2 >>> Reverse Run
- Set Word 48193 = 6 >>> Stop
>>> Set Frequency Address = 1000 (hex) = 4096 (dec) + 40001 = 44097 (dec)
>>> Frequency Reference = (0 to 10000 dec) ~ (0 to VFD Max Frequency)
- Output Frequency Address = 1001 (hex) = 4097 (dec) + 40001 = 44098 (dec)
- Output Voltage Address = 1003 (hex) = 4099 (dec) + 40001 = 44100 (dec)
- Output Current Address = 1004 (hex) = 4100 (dec) + 40001 = 44101 (dec)
PLC Siemens “Modbus RTU” Configuration
We need to set the communication parameters for the PLC similar to those of the Inovance MD200

+ Create Data types

+ Modbus Block Create

PLC Siemens Modbus Example
+ Read and Write Distribution

+ Communication Configuration

+ Frequency Setting

+ VFD Control Command

+ Read Data Response

Project Video Tutorial
======
Related Software and Documents
+ Siemens S7-1200 Programming Software Download
+ Inovance MD200 Inverter Manual Download
Password Extract: plc247.com
Please comment and share the article to the community if you find it useful. Subscribe to Youtube channel and Website to read new articles of plc247.com
Thanks and Best Regards!