Mitsubishi FX5U “Modbus RTU” FUJI Frenic Tutorial

Written by plc247.com

Hello friends! Fuji Frenic inverter is a series of inverters with energy saving functions, simple operation, suitable for a wide range of applications, used in all different applications.

Today plc247.com will guide you to use Mitsubishi FX5U PLC to control FUJI Frenic Series inverter through Modbus RS485 Communication.

Mitsubishi FX5U & FUJI Frenic “Wiring Diagram”

Note: Use a 120Ω terminal resistor if the communication distance is far

FUJI Frenic Modbus RTU Configuration

We need to set the following communication parameters so that the FUJI Frenic inverter can be controlled by Modbus RTU

+ H30 = 3 (Control via RS485 Port)

+ Y01 = 1 ( Slave No.1)

+ Y02 = 0

+ Y03 = 2

+ Y04 = 2 (9600bps)

+ Y05 = 0 (bit)

+ Y06 = 1 (Even)

+ Y07 = 1 ( Stopbit-1)

+ Y10 = 0 (Choose Modbus-RTU)

+ Y99 = 0

FUJI Frenic Registers Table

Here is the Hexa Address corresponding to each group of letters

FUJI Frenic Registers for Control

>>> VFD Frequency Setting Address = S(07Hex) + 05 = 705 (Hexa)

>>> VFD Frequency Control Address = S(07Hex) + 06 = 706 (Hexa)

+ Set Word “706” = 1 >>> Forward Run
+ Set Word “706” = 2 >>> Reverse Run
+ Set Word “706” = 1 >>> Stop

FUJI Frenic Registers for Monitoring

+ Output Frequency Address = M (08H) + 09 = 809 (Hex)

+ Output Voltage Address = M (08H) + 09 = 80C (Hex)

Mitsubishi FX5U Modbus-RTU Setting

We need to configure the same communication parameters as FUJI Frenic VFD

FX5U Modbus-RTU Programming

+ Reset & Control Distribution

+ VFD Control Command

+ VFD Data Monitoring

Project Video Tutorial

======

Documentation Requirements

>>> Download FX5U Programming Software
>>> Download FUJI Frenic Manual PDF

Password Extract: plc247.com

Please comment and share the article to the community if you find it useful. Subscribe to Website and Youtube channel to read new articles of plc247.com

Thanks and Best Regards!