Hello everyone!
In the previous post, plc247.com showed you how to use MicroLogix 1100 PLC to control Mitsubishi FR-E700 Series inverters via RS485 “Modbus-RTU” standard.
Today I would like to continue to guide you to use MicroLogix 1100 PLC to control PowerFlex525 Inverter
Micrologix 1100 & PowerFlex 525 “Wiring Diagram”
![](https://plc247.com/wp-content/uploads/2022/01/micrologix-1100-modbus-rtu-power-flex-525-wiring.jpg)
PowerFlex525 Communication Configurator
In order for the inverter to be controlled via “Modbus-RTU” communication, we need to configure the following minimum parameters:
![](https://plc247.com/wp-content/uploads/2021/12/powerflex-525-modbus-parameters-setting.png)
Register Control Address
![](https://plc247.com/wp-content/uploads/2022/01/powerflex-525-modbus-registers-address.png)
![](https://plc247.com/wp-content/uploads/2021/12/powerflex-525-modbus-registers-address-1.png)
Note: MicroLogix 1100 Address = “VFD Address (Dec) + 1“
>>> Motor Control Address = 8192 (Dec) + 1 = 8193
+ Set Word 8193 = 8 : Reset VFD
= 18 : Forward Run
= 34 : Reverse Run
= 1 : Stop
>>> Motor Frequency Reference Address = 8193 (Dec) + 1 = 8194
Register Monitoring Address
![](https://plc247.com/wp-content/uploads/2021/12/power-felex525-modbus-register-address.png)
We will read the 5 main parameters of the inverter with a single command starting with the following address:
>>> Frequency Command Address = 8450 (Dec) + 1 = 8451
MicroLogix 1100 Modbus RTU Settings
+ Channel Settings
![](https://plc247.com/wp-content/uploads/2022/01/micrologix-1400-msg-instruction-example.png)
MicroLogix 1100 Programming
+ Automatic Read/Write Distribution
![](https://plc247.com/wp-content/uploads/2022/01/micrologix-1100-modbus-rtu-example.png)
+ Control Run Command
![](https://plc247.com/wp-content/uploads/2022/01/micrologix-1100-modbus-rtu-powerflex-525-program-650x1024.png)
+ Frequency Setting Command
![](https://plc247.com/wp-content/uploads/2022/01/micrologix-1100-modbus-rtu-powerflex-525-program-1-765x1024.png)
+ Data Response Monitoring
![](https://plc247.com/wp-content/uploads/2022/01/micrologix-1100-modbus-rtu-powerflex-525-program-2.png)
Video Tutorial
======
References
>>> Download MicroLogix 1100 Manual PDF
>>> Download PowerFlex 525 VFD Manual PDF
Password Extract: plc247.com
Please comment and share the article to the community if you find it useful.
Subscribe to Website and youtube channel to read the latest articles of plc247.com