Hello, in previous posts plc247.com used some PLCs, HMIs to control Siemens Sinamics V20 inverter through Modbus RTU (RS485).
Today plc247.com would like to continue to guide you to use LabView software to control Sinamics V20, this is a software with a beautiful interface and extremely versatile.
Computer & Sinamics V20 “Connection Diagram”
Sinamics V20 Modbus RTU Configuration
We need to set the following communication parameters so that Sinamics V20 can be controlled by Modbus RTU
Registers Control Address
>>> VFD Control Address = 99
+ Set Word 99 = 1151 >>> Forward Run
= 3199 >>> Reverse Run
+ Set Word 99 = 1150 >>> Stop
+ Set Word 99 = 1278 >>> VFD Reset
>>> VFD Frequency Setting Address = 100
Registers Monitoring Address
+ Frequency Output Address = 23
+ Speed Output Address = 24
+ Current Output Address = 25
LabVIEW Modbus Programming
+ Front Panel Design
+ Block Diagram
Video Tutorial
======
>>> Download Siemens Sinamics V20 Manual PDF
Password Extract: plc247.com
Please share the article to the community if you find it useful, comment below the article if you have any questions, plc247.com will reply to you as soon as I read the comments.
Best Regards!
Good Morning.
Is it possible for you to share your vi?
i show 100% program you only need copy