Hello everyone, HMI Delta DOP-107EV is a cheap but very good quality HMI. It supports most of the basic connectivity ports such as Ethernet, RS232, RS422/RS485. In addition to being able to connect to PLCs, it can also connect to devices via Modbus-RTU Communication.
Today plc247.com will guide you to use Delta HMI DOP-107EV to control Fuji Frenic Inverter via Modbus-RTU (Both devices have built-in RS485 port to support Modbus connection)

DOP-107EV & Fuji Frenic Inverter “Wiring Diagram”
+ Below is the connection diagram between HMI and VFD

FUJI Frenic Inverter Modbus Parameters Setting
In order for the Fuji Frenic Mini inverter to be controlled by Modbus-RTU, we need to set the following communication parameters
- H30: 3 (VFD Control via RS485 Port)
- Y01: 1 (Slave Address)
- Y02: 0
- Y03: 2
- Y04: 2 (9600bps)
- Y05: 0 (Data: 8bit)
- Y06: 1 (Parity Check: Even)
- Y07: 1 (Stop Bit: 1)
- Y10: 0 (Modbus-RTU Selection)
- Y99: 0
Fuji Frenic Inverter Modbus Registers Address
+ Functions Group Mapping

+ Registers for Control

+ Registers for Monitoring

- Frequency Setting Address = S(07H) + 05 = 705 (hex)
- Motor Control Address = S(07H) + 06 = 706 (hex)
+ Set Word “706” = 1 >>> Forward Run
= 2 >>> Reverse Run
= 0 >>> Stop Run
- Output Frequency Address = M(08H) + 09 = 809(hex)
Output Voltage Address = M(08H) + 12 = 80C(hex)
Delta HMI Modbus Programming
+ Communicaiton Configuration

+ Control Panel Design

+ Frequency Setting

+ Forward Run Command

+ Reverse Run Command

+ Stop Command

+ Frequency Output Read

+ Voltage Output Read

Project Video Tutorial
======
Related Software and Documents
+ Delta HMI Programming Software Download
+ FUJI Frenic Inverter Manual PDF Download
Password Extract: plc247.com