The Danfoss FC302 is a high-end versatile inverter that can be used in almost any application. It also supports most basic communication protocols including 1 RS485 port and Modbus RTU support.
BToday plc247.com will guide you to control Danfoss FC302 with an extremely light and simple software on your computer, Modbus Poll software. We need to prepare 1 “USB to RS485” Cable
Computer & Danfoss FC302 “Connection Diagram”

Danfoss FC302 Modbus-RTU Configuration
In addition to the basic parameters of the inverter installed according to the motor (frequency, voltage, current …) then we need to install the following communication parameters

Danfoss FC302 Registers Address

>>> VFD Control Address = 49999
- Set Word = 1148 (dec) >>> Run Forward
= 33916 (dec) >>> Run Reverse - Set Word = 1084 (dec) >>> Stop
- Set Word = 1212 (dec) >>> VFD Reset
>>> VFD Speed Setting Address = 50009
Setting Reference = 0 to 16384(dec) ~ (0 to 100%)

Note: Danfoss FC302 Monitoring Address
= “(Table Address*10) – 1“
- Voltage Output Address = 16119
- Frequency Output Address = 16129
- Current Output Address = 16139
- Speed Output Address = 16169
Danfoss FC302 Modbus Example
+ Speed Setting Command

+ VFD Control Command

+ Read Volatge Output

+ Read Frequency Output

+ Read Current Output

+ Read Speed Output

Video Tutorial
======
Related Software and Documents
>>> Modbus Poll Free Download Software
>>> Danfoss FC302 Manual PDF Download
Password Extract: plc247.com
If in the process of making the connection between Modbus Poll and Danfoss FC302 you need any help, please comment below the article, plc247.com will reply to you as soon as I read the comment.
Best Regards!

In help file where can we find modbus addresses? For example VFD Control Address = 49999. I searched manual but unable to find this information.
Please download the document at the bottom of the article
when Modbus poll and VFD communication done then I start the VFD but sometimes later my laptop mouse pad do hang. please help me why laptop mouse pad hang when VFD running. (VFD model: Danfoss FC-102 110KW or Danfoss FC-202 90KW)
You need to fully ground the devices
ok thank you
You do great tutorials. I am suprised that you not made tutorial for relatively cheap siemens Logo8 ( modbus tcp + some tcp/rtu converter) I believe that many of us are interested for that kind of build… I am searching for that solution but no tutorial for combination FC302 danfos with Siemens Logo8 …Best regards.
i will make when i have time sir
Hi , PLC247.COM
Thank you for this great tutorial,
Are Modbus FC32 registers similar to Modbus FC102 registers?
yes, same modbus address sir
Hello Mr, i need your help about the same addresses for vlt 5000,
Can you help me please
same address