Hello friends!
Mitsubishi is a manufacturer of extremely famous automation equipment in the industry and has products that are widely used and popular in the world.
Today plc247.com will guide you to use the Mitsubishi FX5U PLC to control the FR-E700 Series inverter via Modbus RTU (both have built-in 1 RS485 port).
Mitsubishi FX5U & FR-E700 “Connection Diagram”

Note: Use a 120Ω terminal resistor if the communication distance is far
Mitsubishi FR E700 Modbus-RTU Configuration
In order for the FR E700 inverter to be controlled by Modbus RTU, we need to set the parameters as below
+ Pr117: 1 (Slave Address)
+ Pr118: 3 (Baudrate 9600)
+ Pr119: 0 (8bit, stop bit = 1)
+ Pr120: 2 (Even)
+ Pr121: 9999
+ Pr122: 9999
+ Pr123: 9999
Mitsubishi FR-E700 Registers for Control

Note: VFD Address = Starting register address (decimal) – 40001
>>> Control Address = 40009 – 40001 = 8 (dec) = 8 (hex)
- Set Word 8(hex) = 0000 0000 0000 0010 = 2 >>> Forward Run
- Set Word 8(hex) = 0000 0000 0000 0100 = 4 >>> Reverse Run
- Set Word 8(hex) = 0000 0000 0000 0000 = 0 >>> Stop
>>> Set Frequency Address = 40014 – 40001 = 13 (dec) = D (hex)
Mitsubishi FR-E700 Registers for Monitoring

- Output Frequency Address = 40201 – 40001 = 200 (dec) = C8 (hex)
- Output Current Address = C9 (hex)
- Output Voltage Address =CA (hex)
Mitsubishi FX5U Modbus RTU Setting
We need to set communication parameters of Mitsubishi FX5U same as FR-E700 VFD


FX5U Programming Example
+ Reset & Automatic Read / Write

+ VFD Control Command

+ VFD Data Monitoring

Project Video Tutorial
Related Software and Documents
+ Download FX5U Programming Software
+ Mitsubishi FR E700 Manual PDF Download (Password Extract: plc247.com)
If in the process of connecting Mitsubishi FX5U to the FR E700 inverter, you have any problems, please comment below the article, plc247.com will answer you as soon as I read the comment.
Best Regards!

sorry sir can you explain where 40001 come from, If i use different slave device is that still 40001?. thanks
You need to read the inverter’s documentation
can i use this guide for D700 series
same 100% sir
CAN I USE THIS FOR FR CS 80 VFD SERIES AND FOR FX5S PLC?
same this post sir
thank you so much ✌👍
send me videos link sir
go to youtube
Can I use this guide for FX5U as Master and FX5U-32M as slave?
i will make tutorial when i have time sir