Hello friends.
The FX3U PLC is one of the most popular and used PLCs in the world. It is one of Mitsubishi’s most famous PLCs with outstanding advantages and competitive price.
Today plc247.com will guide you to use the FX3U PLC in combination with the FX3U-485ADP-MB Module to control the Siemens Sinamics V20 inverter via Modbus RTU (RS485)
FX3U & Sinamics V20 “Wiring Diagram”

Siemens Sinamics V20 Modbus RTU Setting
In addition to the basic parameters installed according to the motor, we must configure the following communication parameters so that the inverter can be controlled by Modbus RTU

Registers Control

>>> VFD Control Address = 99
+ Set Word 40100 = 1151 >>> Forward Run
= 3199 >>> Reverse Run
= 1150 >>> Stop
+ Set Word 40100 = 1278 >>> VFD Reset
>>> VFD Frequency Reference Address = 100
Registers Monitoring

>>> Frequency Output Address = 23
>>> Speed Output Address = 24
>>> Current Output Address = 25
Mitsubishi FX3U Programming
+ Channel 2 Communication Setting

+ Read/Write Automatic Distribution

+ Frequency Setting Command

+ VFD Control Command

+ Data Monitoring

Detailed Instruction Video
======
Related Software and Documents
+ GX-Works2 for PLC Mitsubishi Programming
+ Download Siemens Sinamics V20 Manual PDF
Password Extract: plc247.com
Please comment and share the article if you find it useful.
Thanks and Best Regards!

How to calculate 1151 from control word table?