Hello everyone, continuing the Series using PLC Inovance H3U to control devices through Modbus-RTU RS485 communication, today plc247.com continues to guide you to control Yaskawa V1000 inverters.
Yaskawa V1000 inverter is a universal inverter and also has a built-in RS485 port for convenient control by Modbus RTU.
PLC Inovance & Yaskawa V1000 “Wiring Diagram”
+ Wiring diagram between PLC Inovance H3U-3232MT and Yaskawa V1000 Inverter
Yaskawa V1000 “Modbus RTU” Parameters Settings
In addition to the basic parameters of the inverter installed according to the motor (voltage, current, frequency…) we need to install the following communication parameters:
Yaskawa V1000 “Modbus RTU” Parameters Address
+ VFD Control Address = 1
- Set Word 2 = 0000 0000 0000 0001 = 1 >>> Forward Run
= 0000 0000 0000 0010 = 2 >>> Reverse Run
= 0000 0000 0000 0000 = 0 >>> Stop
+ Frequency Reference Address = 2
>>> Output Frequency Address = 24 (Hexa)
>>> Output Voltage Address = 25 (Hexa)
>>> Output Frequency Address = 26 (Hexa)
PLC Inovance Modbus Configuration
You need to set up RS485 Port communication parameters. of the Inovance PLC is the same as the Yaskawa V1000 inverter
PLC Programming
+ Add Modbus Config
+ Modbus Address Configuration & Programming
Project Video Tutorial
Below is a video of setting parameters for the inverter and testing the program.
======
Required software and documentation
+ Download Inovance PLC Programming Software
+ Yaskawa V1000 Inverter Manual PDF Download
Password Extract: plc247.com
Comment and share the article to the community if you find it useful. Subscribe to Youtube channel and Website to read new articles of plc247.com
Thanks and Best Regards!
please add Tutorial PLC Panasonic FP-X series with Yaskawa V1000 “Modbus RTU” (RS-485)
i will buy PLC and make tutorial