PLC Inovance “Modbus RTU” Yaskawa V1000 Tutorial

Written by plc247.com

Hello everyone, continuing the Series using PLC Inovance H3U to control devices through Modbus-RTU RS485 communication, today plc247.com continues to guide you to control Yaskawa V1000 inverters.

Yaskawa V1000 inverter is a universal inverter and also has a built-in RS485 port for convenient control by Modbus RTU.

PLC Inovance & Yaskawa V1000 “Wiring Diagram”

+ Wiring diagram between PLC Inovance H3U-3232MT and Yaskawa V1000 Inverter

Yaskawa V1000 “Modbus RTU” Parameters Settings

In addition to the basic parameters of the inverter installed according to the motor (voltage, current, frequency…) we need to install the following communication parameters:

Yaskawa V1000 “Modbus RTU” Parameters Address

+ VFD Control Address = 1

  • Set Word 2 = 0000 0000 0000 0001 = 1 >>> Forward Run
    = 0000 0000 0000 0010 = 2 >>> Reverse Run
    = 0000 0000 0000 0000 = 0 >>> Stop

+ Frequency Reference Address = 2

>>> Output Frequency Address = 24 (Hexa)
>>> Output Voltage Address = 25 (Hexa)
>>> Output Frequency Address = 26 (Hexa)

PLC Inovance Modbus Configuration

You need to set up RS485 Port communication parameters. of the Inovance PLC is the same as the Yaskawa V1000 inverter

PLC Programming

+ Add Modbus Config

+ Modbus Address Configuration & Programming

Project Video Tutorial

Below is a video of setting parameters for the inverter and testing the program.

======

Required software and documentation

+ Download Inovance PLC Programming Software
+ Yaskawa V1000 Inverter Manual PDF Download

Password Extract: plc247.com

Comment and share the article to the community if you find it useful. Subscribe to Youtube channel and Website to read new articles of plc247.com