Mitsubishi FX3U “Modbus RTU” Inovance MD200 Tutorial

Written by plc247.com

Hello everyone! In the previous post, plc247.com showed you how to use some HMIs to control Inovance MD200 inverters via Modbus RTU (RS485).

Today I will continue to guide you to use PLC Mitsubishi FX3U to control Inovance MD200 using Modbus RTU protocol.

Mitsubishi FX3U & Inovance MD200 “Wiring Diagram”

+ RS485 connection diagram between PLC Mitsubishi FX3U and Inovance MD200 inverter.

Inovance MD200 Modbus Parameters Settings

Below are the communication parameters that need to be set up for the Inovance MD200 so that we can control it with Modbus-RTU.

Inovance MD200 Modbus Registers Address

>>> VFD Control Address = 2000 (hexa)

  • Set Word “2000” = 1 >>> Forward Run
  • Set Word “2000” = 2 >>> Reverse Run
  • Set Word “2000” = 6 >>> Stop

>>> Set Frequency Address = 1000 (hexa)
Frequency Reference = (0 to 10000 dec) ~ (0 to VFD Max Frequency)

  • Output Frequency Address = 1001 (hexa)
    Output Voltage Address = 1003 (hexa)
    Output Current Address = 1004 (hexa)

PLC Programming

+ Modbus Parameters Setting & Read/Write Distribution

+ VFD Control Command

+ Data Monitoring

Project Video Tutorial

======

References

+ Download Mitsubishi FX3U Programming Software
+ Inovance MD200 Inverter Manual PDF Download