Hello friends! Fuji Frenic Series is one of the most popular inverters in Japanese machines. With many outstanding advantages and diverse applications, this is a suitable choice for any machine.
Today plc247.com will guide you to implement a project using HMI Proface GP4402WW to connect and control Fuji Frenic VFD through Modbus RTU (RS485) Communication.
Fuji Frenic & GP4402WW “Wiring Diagram”
FUJI Frenic Modbus RTU Parameters Setting
In addition to the basic parameters of the inverter (Frequency, voltage, current…) to be able to control the inverter with Modbus RTU we need to install the following parameters:
- H30 = 3 (VFD Control via RS485 Port)
- Y01 = 1 (Slave Address)
- Y02 = 0
- Y03 = 2
- Y04 = 2 (9600bps)
- Y05 = 0 (data: 8bit)
- Y06 = 1 (parity check: Even)
- Y07 = 1 (stop bit: 1)
- Y10 = 0 (Modbus RTU Selection)
- Y99 = 0
Registers Address Table
Note: GP4402WW HMI Address = “400001 (dec) + Device Address”
- Frequency Setting Address = S(07H) + 05 = 705 (hex)
>>> HMI Address = 400001(dec) + 705(hex) = 400001(dec) + 1797(dec) = 401798
- Motor Control Address = S(07H) + 06 = 706 (hex)
>>> HMI Address = 400001(dec) + 706(hex) = 400001(dec) + 1798(dec) = 401799
+ Set Word 401799 = 1 >>> Forward Run
= 2 >>> Reverse Run
= 0 >>> Stop
Monitoring
- Output Frequency Address = M(08H) + 09 = 809(hex)
>>> HMI Address = 400001(dec) + 809(hex) = 400001(dec) + 2057(dec) = 402058 - Output Voltage Address = M(08H) + 12 = 80C(hex)
>>> HMI Address = 400001(dec) + 80C(hex) = 400001(dec) + 2060(dec) = 402061
HMI Proface Modbus RTU Configuration
The communication parameters to be set are the same as for the Fuji Frenic VFD
HMI Programming
+ Control Panel
+ Frequency Setting
+ Motor Forward Run
+ Motor Reverse Run
+ Stop
+ Frequency Output
+ Voltage Output
Video Tutorial
======
Related Software and Documents
+ HMI Proface Programming Software Download
+ Fuji Frenic Modbus RTU Manual PDF Download (Password: plc247.com)
If you have any problems connecting GP4402WW with FUJI Frenic VFD, please comment below the article, plc247.com will reply to you as soon as possible.
Thanks and Best Regards!
It’s good I have knowledge of Modbus to visit your website. T want to know HMI keyence link modbus rtu with inverter Fuji mini
what model HMI sir ?
its very powerfull video sir.
can you make a video of monitouch hmi communication with vfd through modbus tcp/ip.
i will make when possible