Hello everyone!
In the previous post, plc247.com showed you how to use MicroLogix 1100 PLC to control Mitsubishi FR-E700 Series inverters via RS485 “Modbus-RTU” standard.
Today I would like to continue to guide you to use MicroLogix 1100 PLC to control PowerFlex525 Inverter
Micrologix 1100 & PowerFlex 525 “Wiring Diagram”

PowerFlex525 Communication Configurator
In order for the inverter to be controlled via “Modbus-RTU” communication, we need to configure the following minimum parameters:

Register Control Address


Note: MicroLogix 1100 Address = “VFD Address (Dec) + 1“
>>> Motor Control Address = 8192 (Dec) + 1 = 8193
+ Set Word 8193 = 8 : Reset VFD
= 18 : Forward Run
= 34 : Reverse Run
= 1 : Stop
>>> Motor Frequency Reference Address = 8193 (Dec) + 1 = 8194
Register Monitoring Address

We will read the 5 main parameters of the inverter with a single command starting with the following address:
>>> Frequency Command Address = 8450 (Dec) + 1 = 8451
MicroLogix 1100 Modbus RTU Settings
+ Channel Settings

MicroLogix 1100 Programming
+ Automatic Read/Write Distribution

+ Control Run Command

+ Frequency Setting Command

+ Data Response Monitoring

Video Tutorial
======
References
>>> Download MicroLogix 1100 Manual PDF
>>> Download PowerFlex 525 VFD Manual PDF
Password Extract: plc247.com
Please comment and share the article to the community if you find it useful.
Subscribe to Website and youtube channel to read the latest articles of plc247.com
Thanks and Best Regards!
