Hello friends!
Today plc247.com will write a tutorial on how to control Hitachi NE-S1 Inverter via Modbus-RTU (RS485) with Allen-Bradley MicroLogix 1100 PLC.
Both PLC MicroLogix 1100 and Hitachi NÉ1 VFD have a built-in RS485 port, but for easy wiring we can use additional Module 1763-NC01 for PLC (if not, use directly is also OK).
MicroLogix 1100 & Hitachi NE-S1 “Wiring Diagram”

+ SW5 Select “RS485 Mode”

Hitachi NE-S1 VFD Parameters Setting
To be able to control Hitachi NES1 with Modbus-RTU, in addition to the basic parameters of the inverter, we need to set the following communication parameters:

Hitachi NE-S1 Modbus Registers Map

Note: MicroLogix 1400 Address = “VFD Address (Dec) + 1“
- VFD Run / Stop “Coil Address” = 0 + 1 = “1” (dec)
- VFD Direction Roatation “Coil Address” = 0 + 1 = “2” (dec)
- VFD Trip Reset “Coil Address” = 0 + 3 = “4” (dec)
- VFD Set Frequency “Word Address” = 1 + 1 = “2” (dec)
- VFD Output Frequency “Word Address” = 1 + 4097 = “4098” (dec)
VFD Output Current “Word Address” = 1 + 4098 = “4099” (dec)
VFD Output Voltage “Word Address” = 1 + 4112 = “4113” (dec)
MicroLogix 1100 “Modbus” Configuration
+ For MicroLogix 1100 PLC, Channel.0 is the configuration for RS485 port (MiniDIN-8Pin), we need to set the same communication parameters as Hitachi NES1 VFD

PLC Programming
+ Auto Distribution

+ Set Frequency Command

+ VFD Run / Stop Control

+ VFD Direction Control

+ VFD Reset Control

+ Data Monitoring




Project Video Tutorial
======
References
+ Allen-Bradley MicroLogix 1100 Manual PDF Download
+ Hitachi NE-S1 VFD Manual PDF Download
Password Extract: plc247.com
Please comment and share the article to the community if you find it useful. Subscribe to Youtube channel and Website to read new articles of plc247.com
Thanks and Best Regards!