Hello friends!
Today plc247.com would like to continue the series of instructions for using the Mitsubishi GT2505-VTBD HMI to control various devices through the Modbus RTU communication protocol, I will continue to guide you to control the Allen-Bradley PowerFlex inverter.
The inverter model used is Allen-Bradley PowerFlex 525, this is one of the most commonly used models on the market (other models with the same control series are similar)

HMI Mitsubishi & PowerFlex 525 “Wiring Diagram”
Connection Diagram

Allen-Bradley PowerFlex 525 Parameters Setting
Below are the communication parameters that need to be installed for the PowerFlex 525 inverter so that we can control and monitor it with Modbus-RTU.

Modbus Registers Mapping




Note: Mitsubishi GOT2000 Holding Registers Address =
“VFD Address (Dec) + 400001“
>>> Motor Control Address = 8192 (dec) + 400001 = 408193 (dec)
- Set Word 408193 = 18 (dec) >>> Run Forward
- Set Word 408193 = 34 (dec) >>> Run Reverse
- Set Word 408193 = 1 (dec) >>> Stop
= 8 (dec) >>> VFD Fault Reset
>>> Frequency Setting Address = 8193 (dec) + 400001 = 408194 (dec)
>>> VFD Status Address = 8448 (dec) + 400001 = 408449 (dec)
+ Output Frequency Address = 8451 (dec) + 400001 = 408452 (dec)
+ Output Current Address = 8452 (dec) + 400001 = 408453 (dec)
+ Output Voltage Address = 8454 (dec) + 400001 = 408455 (dec)
Mitsubishi GT2505-VTBD Modbus Configuration
We need to set the communication parameters for the Mitsubishi HMI inverter the same as those installed for the PowerFlex 525 inverter.



HMI Mitsubishi Programming
+ HMI Design

+ VFD “Ready” Status

+ VFD “Running” Status

+ VFD “Alarm” Status

+ VFD Reset Command

+ Frequency Setting

+ Forward Run Command

+ Reverse Run Command

+ Stop Command

+ Output Frequency Read

+ Output Current Read

+ Output Voltage Read

Project Video Tutorial
======
Related Software and Documents
+ Mitsubishi GT-Designer 3 Software Free Download
+ PowerFlex 525 Inverter Manual PDF Download
(Password Extract: plc247.com)
Subscribe to Youtube channel and Website to read new articles of plc247.com, comment and share the article to the community if you find it interesting and useful.
Thanks and Best Regards!