PLC Guides Sensor Guides

MicroLogix 1400 “Modbus RTU” Autonics TK4S Tutorial

Written by plc247.com

Hello friends!
In the previous article plc247.com wrote a tutorial on how to use MicroLogix 1400 to connect and control Omron E5CC Controller, today I will continue to guide you to use MicroLogix 1400 to control another Temperature Controller is Autonics TK4S.

In this project plc247.com uses MicroLogix PLC Model “1766-L32BXB” and Autonics Controller Model “TK4S-T4SN“. Please pay attention to choose to buy Model Autonics TK4S with RS485 communication support, then we can control it with Modbus RTU

MicroLogix 1400 & Autonics TK4S “Wiring Diagram”

+ You can wire it directly through the MiniDIN-8Pin port or use the 1763-NC01 Module for easier wiring

+ If the communication distance is long, we need to add a 120(Ω) Terminal Resistor

Autonics TK4S “Modbus RTU” Parameters Setting

Below is a table of Modbus RTU (RS485) communication parameters that need to be installed for Autonics TK4S Controller, you can install the same as plc247.com installed.

TK4S >>> Mode >>> PAr.4

+ AdrS = 1 (Modbus Slave)

+ bPS = 9.6 (9600bps)

+ Prty = EvEn (Parity check)

+ StP = 1 (Stop bit)

+ rSy.t = 20 (Response time)

Autonics TK4S Registers Address
Note: MicroLogix 1400 Address = “VFD Address (Dec) + 1

+ Register Address for Set Temperature

  • Funtion Code = 06
  • Address = 0000 + 1 = 1

+ Register Address for Temperature Monitoring

  • Funtion Code = 04
  • Address = 03E8 (hex) + 1 = 1000 (dec) + 1 = 1001

MicroLogix 1400 “PLC Programming”

+ Read/Write Distribution

+ Autonics TK4S Modbus-RTU Control

+ TK4S (1) Temperature Setting

+ TK4S (2) Temperature Setting

+ TK4S (1) Temperature Read

+ TK4S (2) Temperature Read

Detailed Instruction Video

======

Documents Reference

>>> MicroLogix 1400 Manual PDF Download
>>> Autonics TK4S Manual PDF Download

Password Extract: plc247.com

Please share the article to the community if you find it useful, subscribe to Youtube channel and Website to read new articles of plc247.com

Thanks and Best Regards!

About the author

plc247.com

Leave a Comment